Additional Information
- Part Number
- 8965360000
Probability Of Failure
- MTBF
- 215 Years
- SIL PAPER
- SIL certificate
Digital Output
- Type
- NPN-Transitor, Switching frequency 5 kHz
- Nominal switching voltage
- 30 V DC
- Continuous current
- 80 mA
- Function
- Output = input, direct or inverse (configurable)
Approvals
- ROHS
- Conform
- UL File Number Search
- E337701
Dimensions And Weights
- Width
- 22.5 mm
- Width (inches)
- 0.886 inch
- Height
- 119.2 mm
- Height (inches)
- 4.693 inch
- Depth
- 113.6 mm
- Depth (inches)
- 4.472 inch
- Net weight
- 170 g
Safety-Related Specifications Low Demand Mode
- Average Probability of Failure on Demand (PFD
- 1.58 x 10-4 (Tproof = 1 year), 3.17 x 10-4 (Tproof = 2 years), 7.92 x 10-4 (Tproof = 5 years)
Connection Data
- Type of connection
- Screw connection
- Tightening torque, min.
- 0.4 Nm
- Tightening torque, max.
- 0.6 Nm
- Clamping range, rated connection
- 2.5 mm²
- Clamping range, min.
- 0.25 mm²
- Clamping range, max.
- 2.5 mm²
- Wire connection cross section AWG, min.
- AWG 26
- Wire connection cross section AWG, max.
- AWG 12
Rated Data Ul
- UL certificate
- E337701.pdf
Safety-Related Basic Specifications
- Demand mode
- High
- Demand rate
- 1,000 s
- Description of the "safe state"
- High impedance
- Device type
- B
- Diagnostic test interval
- 10 s
- Hardware fault tolerance (HFT)
- 0
- Mean Time To Repair (MTTR)
- 8 h
- Safe Failure Fraction (SFF)
- 92 %
- T
- 5 Years
- Total failure rate for dangerous detected failures (»
- 135 FIT
- Total failure rate for dangerous undetected failures (»
- 36 FIT
- Total failure rate for safe detected failures (»
- 0 FIT
- Total failure rate for safe undetected failures (»
- 275 FIT
- Safety category
- SIL 2
- Probability of outage PFH
- 3.62 x 10-8 h-1
Tender Specification Sheets
- Long specification
- Ex isolating switch amplifiers for Namur sensors,1-channel isolating switch amplifiers in 22.5 mm width with an external power supply,to transmit and isolate Namur sensor signals from Ex zones 0,1, 2 into the safe zone. On the output side there is an NPN switching transistor and a common alarm contact (relay/"a" contact) for status or error messages.The component can be configured using standard FDT/DTM software.Add-on housing for TS35 DIN rail installationDimensions: L/W/H 119.2/ 22.5/ 113.6screw connection/ nominal cross-section 2.5 mm2Protection degree: IP20 Input NAMUR sensor according to EN 60947 8 VDC / 8 mA sensor power supply 0 to 5 kHz input frequency wire-break detectionOutput NPN transistor 30 VDC @ 80 mA 5 kHz switching frequency < 2, 5 VDC SpannungsfallAlarm output relay 1 NO contact 250 VAC / 30 VDC @ 2A safe zone 32 VAC @ 0.5 A/ 32 VDC @ 1 A zone 2Auxiliary power 19...31.2 VDCPower loss approx. 1.8 WAmbienttemperature range -20°C to +60°CSecure isolation EN 61010, 3-way isolation up to 2.6 kV AC/DC of all circuits against each otherWorking voltage 300 V AC/DC at overvoltage category II and pollution degree 2Approvals cULus, ATEX IECEX, FM ATEX marking II 3 G ExnA nC IIC T4 ATEX characteristic data U0 = 10, 6 V DC I0 = 12 mA DC P0 = 32 WType ACT20X-HDI-2SDO-2SDO-S
- Short specification
- Ex isolating switch amplifiers for Namur sensors,1-channel isolating switch amplifiers in 22.5 mm width with an external power supply,to transmit and isolate Namur sensor signals from Ex zones 0,1, 2 into the safe zone. On the output side there is an NPN switching transistor and a common alarm contact (relay/"a" contact) for status or error messages.The component can be configured using standard FDT/DTM software.
Alarm Output
- Alarm function
- Line interruption at the input, Short circuit at input, No supply voltage, Device error
- Type
- Relay, 1 NC (voltage-free)
- Nominal switching voltage
- ‰¤ 125 V AC / 110 V DC (safe area)‰¤ 32 V AC / 32 V DC (zone 2)
- Continuous current
- ‰¤ 0.5 A AC / 0.3 A DC (safe zone), ‰¤ 0,5 A AC / 1 A DC (zone 2)
- Power rating
- ‰¤ 62.5 VA / 32 W (safe area)‰¤ 16 VA / 32 W (Zone 2)
Classifications
- ETIM 6.0
- EC002653
- ETIM 7.0
- EC002653
- EClass 9.0
- 27-21-01-20
- EClass 9.1
- 27-21-01-20
- EClass 10.0
- 27-21-01-20
- UNSPSC
- 30-21-18-01
Output
- Influence of load resistance
- ‰¤ 0.01% of span / 100 ©
Product Information
- Product information
- Weidmüller provides an extended guarantee period of 36 months for this device.
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
Data For Ex Applications (Atex)
- Voltage U
- 10.6 V DC
- Current I
- 12 mA DC
- Power P
- 32 mW
- Marking
- II (1) G [Ex ia Ga] IIC/IIB/IIA, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
- Installation location
- Device installed in safe area, zone 2
Insulation Coordination
- EMC standards
- DIN EN 61326, NE 21
- Insulation voltage
- 2.6 kV (input / output)
- Rated voltage
- 300 V
Input Ex
- Input frequency
- 0...5 kHz
- Input resistance
- 1 k©
- Output signal in case of wire break
- < 0.1 mA, > 6.5 mA (in case of wire break)
- Pulse duration
- > 0.1 ms
- Resistance
- Series resistor 750©, Parallel resistor 15k©
- Sensor
- NAMUR sensor, according to EN60947, switch with or without RS, RP
- Sensor supply
- 8 V DC / 8 mA
- Trigger level high
- > 2.1 mA
- Trigger level low
- < 1.2 mA
- Type
- intrinsically safe circuit
Temperatures
- Humidity
- 0...95 % (no condensation)
- Operating temperature, max.
- 60 °C
- Operating temperature, min.
- -20 °C
- Storage temperature, max.
- 85 °C
- Storage temperature, min.
- -20 °C
- Operating temperature
- -20°C...60°C
- Storage temperature
- -20°C...85°C
Ratings Iecex/Atex/Cul
- ATEX certificate
- 09ATEX0168X.pdf
- IEC Ex certificate
- IECEx certification
- Certificate No. (ATEX)
- KEMA09ATEX0168X
- Certificate No. (IECEX)
- IECEXKEM09.0072X
- Certificate no. (cULus)
- E337701
General Specifications
- Configuration
- With FDT/DTM software
- Voltage supply
- 19.2€¦31.2 V DC
- Type of connection
- Screw connection
- NAMUR supply
- 8 V DC / 8 mA
- Power consumption
- ‰¤ 1.1 W
- Protection degree
- IP20
- Humidity
- 0...95 % (no condensation)