Additional Information
- Part Number
- 2456150000
Probability Of Failure
- MTBF
- 315 Years
- SIL PAPER
- SIL certificate
Approvals
- Approvals
- DNV GL, EAC
- ROHS
- Conform
Dimensions And Weights
- Width
- 22.5 mm
- Width (inches)
- 0.886 inch
- Height
- 127.3 mm
- Height (inches)
- 5.012 inch
- Depth
- 114.6 mm
- Depth (inches)
- 4.512 inch
- Net weight
- 212 g
Safety-Related Specifications Low Demand Mode
- Average Probability of Failure on Demand (PFD
- 1.92 x 10-4 (Tproof = 1 year), 3.67 x 10-4 (Tproof = 2 years), 8.92 x 10-4 (Tproof = 5 years), additional data in the safety manual
Connection Data
- Type of connection
- PUSH IN
- Wire connection cross section AWG, min.
- AWG 26
- Wire connection cross section AWG, max.
- AWG 14
- Wire cross-section, solid, min.
- 0.2 mm²
- Wire cross-section, solid, max.
- 2.5 mm²
- Wire connection cross-section, finely stranded, min.
- 0.2 mm²
- Wire connection cross section, finely stranded, max.
- 2.5 mm²
- Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min.
- 0.2 mm²
- Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max.
- 2.5 mm²
Rated Data Ul
- UL certificate
- E337701.pdf
Safety-Related Basic Specifications
- Demand mode
- High
- Description of the "safe state"
- analogue Output ? 3.6 mA or output ? 21 mA
- Device type
- A
- Hardware fault tolerance (HFT)
- 0
- Mean Time To Repair (MTTR)
- 24 h
- Safe Failure Fraction (SFF)
- 85 %
- T
- 5 Years
- Total failure rate for dangerous detected failures (?
- 127 FIT
- Total failure rate for dangerous undetected failures (?
- 48 FIT
- Total failure rate for safe detected failures (?
- 0 FIT
- Total failure rate for safe undetected failures (?
- 164 FIT
- Safety category
- SIL 2
- Probability of outage PFH
- 4.1 x 10-8 h-1
Alarm Output
- Alarm function
- Signal limit exceeded, Line interruption at the input, No supply voltage, Device error
- Type
- Relay, 1 NC (voltage-free)
- Nominal switching voltage
- ? 125 V AC / 110 V DC (safe area)? 32 V AC / 32 V DC (zone 2)
- Continuous current
- ? 0.5 A AC / 0.3 A DC (safe zone), ? 0,5 A AC / 1 A DC (zone 2)
- Power rating
- ? 62.5 VA / 32 W (safe area)? 16 VA / 32 W (Zone 2)
Classifications
- ETIM 6.0
- EC002653
- ETIM 7.0
- EC002653
- EClass 9.0
- 27-21-01-20
- EClass 9.1
- 27-21-01-90
- EClass 10.0
- 27-21-01-20
Output
- Load stability
- ? 0.01 % of end value / 100 ?
- Type
- active (as current source) or passive (as current sink)
- Influence of load resistance
- ? 0.01% of span / 100 ?
- 2-wire supply
- ? 26 V DC
- Output signal limit
- < 28 mA
- Output current
- 4...20 mA
- Cut-off frequency (-3 dB)
- 0.5…2.5 kHz @ 3.5…23 mA bi-directional HART® signal
- Load impedance current
- ? 600 ?
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
Data For Ex Applications (Atex)
- Voltage U
- Current loop 28 V / externally 10 V
- Current I
- Current loop 93 mA / externally 10 mA
- Power P
- Current loop 0.65 W / externally 0.1 W
- Marking
- II (1) G [Ex ia Ga] IIC/IIB/IIA, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
- Installation location
- Device installed in safe area, zone 2
Insulation Coordination
- EMC standards
- DIN EN 61326, NE 21
- Insulation voltage
- 2.6 kV (input / output)
- Rated voltage
- 300 V
Input Ex
- Input current
- 4…20mA
- Input frequency
- 0,5…2,5 kHz @ 3,5…23 mA bi-directional HART® signal
- Output signal in case of wire break
- < 1 mA
- Residual ripple (current loop)
- < 7.5 mVeff
- Sensor supply
- 3.8…26 V DC
- Type
- intrinsically safe circuit, active (as current source) or passive (as current sink)
- Voltage drop not powered
- < 6 V
- Voltage drop powered
- < 4.5 V
Temperatures
- Humidity
- 0...95 % (no condensation)
- Operating temperature, max.
- 60 °C
- Operating temperature, min.
- -20 °C
- Storage temperature, max.
- 85 °C
- Storage temperature, min.
- -20 °C
- Operating temperature
- -20 °C...60 °C
- Storage temperature
- -20 °C...85 °C
Ratings Iecex/Atex/Cul
- ATEX certificate
- 11ATEX0131X.pdf
- IEC Ex certificate
- IECEx certification
General Specifications
- Configuration
- With FDT/DTM software
- Voltage supply
- 19.2…31.2 V DC
- Type of connection
- PUSH IN
- Power consumption
- ? 1.9 W
- Accuracy
- < 0.1% span
- Temperature coefficient
- < 0.01% of span/°C (TU)
- Step response time
- ? 5 ms
- Protection degree
- IP20
- Humidity
- 0...95 % (no condensation)