Additional Information Part Number 2456100000 Probability Of Failure MTBF 215 Years SIL PAPER SIL certificate Digital Output Type NPN-Transitor, Switching frequency 5 kHz Nominal switching voltage 30 V DC Continuous current 80 mA Function Output = input, direct or inverse (configurable) Approvals Approvals DNV GL, EAC ROHS Conform Dimensions And Weights Width 22.5 mm Width (inches) 0.886 inch Height 127.3 mm Height (inches) 5.012 inch...

Additional Information

Part Number
2456100000

Probability Of Failure

MTBF
215 Years
SIL PAPER
SIL certificate

Digital Output

Type
NPN-Transitor, Switching frequency 5 kHz
Nominal switching voltage
30 V DC
Continuous current
80 mA
Function
Output = input, direct or inverse (configurable)

Approvals

Approvals
DNV GL, EAC
ROHS
Conform

Dimensions And Weights

Width
22.5 mm
Width (inches)
0.886 inch
Height
127.3 mm
Height (inches)
5.012 inch
Depth
114.6 mm
Depth (inches)
4.512 inch
Net weight
20 g

Safety-Related Specifications Low Demand Mode

Average Probability of Failure on Demand (PFD
1.58 x 10-4 (Tproof = 1 year), 3.17 x 10-4 (Tproof = 2 years), 7.92 x 10-4 (Tproof = 5 years)

Connection Data

Type of connection
PUSH IN
Wire connection cross section AWG, min.
AWG 26
Wire connection cross section AWG, max.
AWG 14
Wire cross-section, solid, min.
0.2 mm²
Wire cross-section, solid, max.
2.5 mm²
Wire connection cross-section, finely stranded, min.
0.2 mm²
Wire connection cross section, finely stranded, max.
2.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min.
0.2 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max.
2.5 mm²

Rated Data Ul

UL certificate
E337701.pdf

Safety-Related Basic Specifications

Demand mode
High
Demand rate
1,000 s
Description of the "safe state"
High impedance
Device type
B
Diagnostic test interval
10 s
Hardware fault tolerance (HFT)
0
Mean Time To Repair (MTTR)
8 h
Safe Failure Fraction (SFF)
92 %
T
5 Years
Total failure rate for dangerous detected failures (?
135 FIT
Total failure rate for dangerous undetected failures (?
36 FIT
Total failure rate for safe detected failures (?
0 FIT
Total failure rate for safe undetected failures (?
275 FIT
Safety category
SIL 2
Probability of outage PFH
3.62 x 10-8 h-1

Alarm Output

Alarm function
Line interruption at the input, Short circuit at input, No supply voltage, Device error
Type
Relay, 1 NC (voltage-free)
Nominal switching voltage
? 125 V AC / 110 V DC (safe area)? 32 V AC / 32 V DC (zone 2)
Continuous current
? 0.5 A AC / 0.3 A DC (safe zone), ? 0,5 A AC / 1 A DC (zone 2)
Power rating
? 62.5 VA / 32 W (safe area)? 16 VA / 32 W (Zone 2)

Classifications

ETIM 6.0
EC002653
ETIM 7.0
EC002653
EClass 9.0
27-21-01-20
EClass 9.1
27-21-01-20
EClass 10.0
27-21-01-20

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Data For Ex Applications (Atex)

Voltage U
10.6 V DC
Current I
12 mA DC
Power P
32 mW
Marking
II (1) G [Ex ia Ga] IIC/IIB/IIA, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
Installation location
Device installed in safe area, zone 2

Insulation Coordination

EMC standards
DIN EN 61326, NE 21
Insulation voltage
2.6 kV (input / output)
Rated voltage
300 V

Input Ex

Input frequency
0...5 kHz
Input resistance
1 k?
Output signal in case of wire break
< 0.1 mA, > 6.5 mA (in case of wire break)
Pulse duration
> 0.1 ms
Resistance
Parallel resistor 15k?, Series resistor 750?
Sensor
NAMUR sensor, according to EN60947, switch with or without RS, RP
Sensor supply
8 V DC / 8 mA
Trigger level high
> 2.1 mA
Trigger level low
< 1.2 mA
Type
intrinsically safe circuit

Temperatures

Humidity
0...95 % (no condensation)
Operating temperature, max.
60 °C
Operating temperature, min.
-20 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-20 °C
Operating temperature
-20 °C...60 °C
Storage temperature
-20 °C...85 °C

Ratings Iecex/Atex/Cul

ATEX certificate
09ATEX0168X.pdf
IEC Ex certificate
IECEx certification

General Specifications

Configuration
With FDT/DTM software
Voltage supply
19.2…31.2 V DC
Type of connection
PUSH IN
NAMUR supply
8 V DC / 8 mA
Power consumption
? 1.5 W
Protection degree
IP20
Humidity
0...95 % (no condensation)

Returns Policy

You may return most new, unopened items within 30 days of delivery for a full refund. We'll also pay the return shipping costs if the return is a result of our error (you received an incorrect or defective item, etc.).

You should expect to receive your refund within four weeks of giving your package to the return shipper, however, in many cases you will receive a refund more quickly. This time period includes the transit time for us to receive your return from the shipper (5 to 10 business days), the time it takes us to process your return once we receive it (3 to 5 business days), and the time it takes your bank to process our refund request (5 to 10 business days).

If you need to return an item, simply login to your account, view the order using the "Complete Orders" link under the My Account menu and click the Return Item(s) button. We'll notify you via e-mail of your refund once we've received and processed the returned item.

Shipping

We can ship to virtually any address in the world. Note that there are restrictions on some products, and some products cannot be shipped to international destinations.

When you place an order, we will estimate shipping and delivery dates for you based on the availability of your items and the shipping options you choose. Depending on the shipping provider you choose, shipping date estimates may appear on the shipping quotes page.

Please also note that the shipping rates for many items we sell are weight-based. The weight of any such item can be found on its detail page. To reflect the policies of the shipping companies we use, all weights will be rounded up to the next full pound.

Recently Viewed Products