Additional Information
- Part Number
- 2456070000
Probability Of Failure
- MTBF
- 215 Years
- SIL PAPER
- SIL certificate
Digital Output
- Type
- NPN-Transitor, Switching frequency 5 kHz
- Nominal switching voltage
- 30 V DC
- Continuous current
- 80 mA
- Function
- Output = input, direct or inverse (configurable)
Approvals
- Approvals
- DNV GL, EAC
- ROHS
- Conform
Dimensions And Weights
- Width
- 22.5 mm
- Width (inches)
- 0.886 inch
- Height
- 127.3 mm
- Height (inches)
- 5.012 inch
- Depth
- 114.6 mm
- Depth (inches)
- 4.512 inch
- Net weight
- 170 g
Safety-Related Specifications Low Demand Mode
- Average Probability of Failure on Demand (PFD
- 1.58 x 10-4 (Tproof = 1 year), 3.17 x 10-4 (Tproof = 2 years), 7.92 x 10-4 (Tproof = 5 years)
Connection Data
- Type of connection
- PUSH IN
- Wire connection cross section AWG, min.
- AWG 26
- Wire connection cross section AWG, max.
- AWG 14
- Wire cross-section, solid, min.
- 0.2 mm²
- Wire cross-section, solid, max.
- 2.5 mm²
- Wire connection cross-section, finely stranded, min.
- 0.2 mm²
- Wire connection cross section, finely stranded, max.
- 2.5 mm²
- Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min.
- 0.2 mm²
- Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max.
- 2.5 mm²
Rated Data Ul
- UL certificate
- E337701.pdf
Safety-Related Basic Specifications
- Demand mode
- High
- Demand rate
- 1,000 s
- Description of the "safe state"
- High impedance
- Device type
- B
- Diagnostic test interval
- 10 s
- Hardware fault tolerance (HFT)
- 0
- Mean Time To Repair (MTTR)
- 8 h
- Safe Failure Fraction (SFF)
- 92 %
- T
- 5 Years
- Total failure rate for dangerous detected failures (»
- 135 FIT
- Total failure rate for dangerous undetected failures (»
- 36 FIT
- Total failure rate for safe detected failures (»
- 0 FIT
- Total failure rate for safe undetected failures (»
- 275 FIT
- Safety category
- SIL 2
- Probability of outage PFH
- 3.62 x 10-8 h-1
Alarm Output
- Alarm function
- Line interruption at the input, Short circuit at input, No supply voltage, Device error
- Type
- Relay, 1 NC (voltage-free)
- Nominal switching voltage
- ‰¤ 125 V AC / 110 V DC (safe area)‰¤ 32 V AC / 32 V DC (zone 2)
- Continuous current
- ‰¤ 0.5 A AC / 0.3 A DC (safe zone), ‰¤ 0,5 A AC / 1 A DC (zone 2)
- Power rating
- ‰¤ 62.5 VA / 32 W (safe area)‰¤ 16 VA / 32 W (Zone 2)
Classifications
- ETIM 6.0
- EC002653
- ETIM 7.0
- EC002653
- EClass 9.0
- 27-21-01-20
- EClass 9.1
- 27-21-01-20
- EClass 10.0
- 27-21-01-20
Output
- Influence of load resistance
- ‰¤ 0.01% of span / 100 ©
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
Data For Ex Applications (Atex)
- Voltage U
- 10.6 V DC
- Current I
- 12 mA DC
- Power P
- 32 mW
- Marking
- II (1) G [Ex ia Ga] IIC/IIB/IIA, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
- Installation location
- Device installed in safe area, zone 2
Insulation Coordination
- EMC standards
- DIN EN 61326, NE 21
- Insulation voltage
- 2.6 kV (input / output)
- Rated voltage
- 300 V
Input Ex
- Input frequency
- 0...5 kHz
- Input resistance
- 1 k©
- Output signal in case of wire break
- < 0.1 mA, > 6.5 mA (in case of wire break)
- Pulse duration
- > 0.1 ms
- Resistance
- Series resistor 750©, Parallel resistor 15k©
- Sensor
- NAMUR sensor, according to EN60947, switch with or without RS, RP
- Sensor supply
- 8 V DC / 8 mA
- Trigger level high
- > 2.1 mA
- Trigger level low
- < 1.2 mA
- Type
- intrinsically safe circuit
Temperatures
- Humidity
- 0...95 % (no condensation)
- Operating temperature, max.
- 60 °C
- Operating temperature, min.
- -20 °C
- Storage temperature, max.
- 85 °C
- Storage temperature, min.
- -20 °C
- Operating temperature
- -20 °C...60 °C
- Storage temperature
- -20 °C...85 °C
Ratings Iecex/Atex/Cul
- ATEX certificate
- 09ATEX0168X.pdf
- IEC Ex certificate
- IECEx certification
General Specifications
- Configuration
- With FDT/DTM software
- Voltage supply
- 19.2€¦31.2 V DC
- Type of connection
- PUSH IN
- NAMUR supply
- 8 V DC / 8 mA
- Power consumption
- ‰¤ 1.1 W
- Protection degree
- IP20
- Humidity
- 0...95 % (no condensation)