WEIDMULLER 1453210000-Dropship Automation

WEIDMULLER 1453210000

SKU: DA-383152
Availability: 1 In Stock
Product Type: simple
Additional Information Part Number 1453210000 General Data Accuracy < 0.1 % of measuring range Cold-junction compensation error ±1.0°C @ -20° C - 65°C Configuration With FDT/DTM software Galvanic isolation 2-way isolator, between input/output Rail TS 35 Step response time 450 ms Temperature coefficient < 0.02°C of measuring range /°C Voltage supply Output loop powered, (10¦45 V) Approvals ROHS Conform Dimensions...

Additional Information

Part Number
1453210000

General Data

Accuracy
< 0.1 % of measuring range
Cold-junction compensation error
±1.0°C @ -20° C - 65°C
Configuration
With FDT/DTM software
Galvanic isolation
2-way isolator, between input/output
Rail
TS 35
Step response time
450 ms
Temperature coefficient
< 0.02°C of measuring range /°C
Voltage supply
Output loop powered, (10¦45 V)

Approvals

ROHS
Conform

Dimensions And Weights

Width
12.5 mm
Width (inches)
0.492 inch
Height
119.2 mm
Height (inches)
4.693 inch
Depth
113.6 mm
Depth (inches)
4.472 inch
Net weight
157 g

Output (Digital)

Type
Transistor, open collector
Rated switching current
20 mA
Rated switching voltage
‰¤ 30 V DC

Connection Data

Type of connection
Screw connection
Tightening torque, min.
0.4 Nm
Tightening torque, max.
0.6 Nm
Clamping range, rated connection
2.5 mm²
Clamping range, min.
0.5 mm²
Clamping range, max.
2.5 mm²
Wire connection cross section AWG, min.
AWG 26
Wire connection cross section AWG, max.
AWG 12

Input

Number of inputs
1
Type
Universal signal isolator / signal amplifier, thermocouple, RTD
Sensor
PT100 / 2-/3-/4-wire, PT1000/2-/3-/4-wire, PT200, N120, Thermocouples: B, E, J, K, L, N, R, S, T, U
Sensor supply
0.1 mA / 0.05 mA (depending on measuring range) @ RTD cable
Influence of the sensor cable resistance
5 © @ RTD- Kabel
Input voltage
configurable, ± 300 V DC (min. measurement range 100 V), 0...300 V AC (min. measurement range 100 V)
Input resistance, voltage
2 M©, > 10 M©
Input current
configurable, ± 5 A DC (min. measurement range 0.5 A)
Input resistance, current
40 ©
Input measurement range
PT100 -200¦+850°C, Thermocouple type J -100¦+1200°C, Thermocouple type K -200¦+1370°C, customerization
Cable-length compensation
< ±0.002 © per cable resistance ©
Resistance
0¦750 ©, 0¦1.5 k©, 0¦12 k©
Potentiometer
1.2¦500 k©

Classifications

ETIM 6.0
EC002653
ETIM 7.0
EC002653
EClass 9.0
27-21-01-20
EClass 9.1
27-21-01-90
EClass 10.0
27-21-01-20

Output

Type
Output-loop powered
Number of outputs
1
Output signal limit
Harmonics: <10 mV (peak to peak)
Output current
4...20 mA, 20¦4 mA, Current loop
Cold junction compensation
‰¤±1°C (-20°C¦60°C)
Load impedance current
typ. 700 © @ 24 V DC
Supply voltage (output)
via output current loop

Product Information

Product information
The ACT20P-UI-AO-DO-LP-X converts and isolates current, voltage, potentiometer and temperature sensor signals (mA, A, mV, V, potentiometer, RTD and TC). The transmit function between the input and output can be set via the configuration program either to predefined functions (x0.5, x, x2) or via a freely definable function table. The device is powered via the output current loop. Features Configuration and monitoring are performed via FDT/DTM-Software žWI-Managerœ. The active or passive signal inputs for RTD, TC, potentiometer, mV, V, mA and A are completely electrically isolated. The TC signal input has internal cold-junction compensation. Alarm output (for example, for limit monitoring, sensor error detection and more) 3-way galvanic isolation between input, output/supply and alarm output.

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Insulation Coordination

Galvanic isolation
2-way isolator, between input/output
Impulse withstand voltage
4 kV (1.2/50 µs)
Insulation voltage
3.51 kV between input and output
Pollution severity
2
Rated voltage
300 Veff
Surge voltage category
III

Temperatures

Humidity
10¦90 %, no condensation
Operating temperature, max.
70 °C
Operating temperature, min.
-20 °C
Storage temperature, max.
70 °C
Storage temperature, min.
-20 °C
Operating temperature
-20°C...70°C
Ambient temperature
-20°C...+70°C
Storage temperature
-20°C...70°C

Returns Policy

You may return most new, unopened items within 30 days of delivery for a full refund. We'll also pay the return shipping costs if the return is a result of our error (you received an incorrect or defective item, etc.).

You should expect to receive your refund within four weeks of giving your package to the return shipper, however, in many cases you will receive a refund more quickly. This time period includes the transit time for us to receive your return from the shipper (5 to 10 business days), the time it takes us to process your return once we receive it (3 to 5 business days), and the time it takes your bank to process our refund request (5 to 10 business days).

If you need to return an item, simply login to your account, view the order using the "Complete Orders" link under the My Account menu and click the Return Item(s) button. We'll notify you via e-mail of your refund once we've received and processed the returned item.

Shipping

We can ship to virtually any address in the world. Note that there are restrictions on some products, and some products cannot be shipped to international destinations.

When you place an order, we will estimate shipping and delivery dates for you based on the availability of your items and the shipping options you choose. Depending on the shipping provider you choose, shipping date estimates may appear on the shipping quotes page.

Please also note that the shipping rates for many items we sell are weight-based. The weight of any such item can be found on its detail page. To reflect the policies of the shipping companies we use, all weights will be rounded up to the next full pound.

Recently Viewed Products