Additional Information
- Part Number
- 1423550000
Approvals
- Approvals
- CE
- ROHS
- Conform
Communication
- Interface
- RS485: Autobaud, 9,6 - 115.2 kbps (pluggable screw terminals)
- Protocol
- Modbus RTU
Dimensions And Weights
- Width
- 96 mm
- Width (inches)
- 3.78 inch
- Height
- 96 mm
- Height (inches)
- 3.78 inch
- Depth
- 68 mm
- Depth (inches)
- 2.677 inch
- Net weight
- 427 g
Measurement Data Recording
- Memory; minimum and maximum values
- No
- Software
- Power Monitor Manager
- Integrated logic
- No
Voltage Quality Measurement
- Positive, negative and zero system
- Yes
- Brief interruptions
- Yes
- Sequence-of-events recorder function
- No
Tender Specification Sheets
- Long specification
- Electrical parameters have to be measured and visualised to optimise your machines' and systems' energy needs. This is the only way in which an analysis can be carried out and, subsequently, savings made and an energy management system established. An easy-to-install solution is now available from Weidm¼ller. When implementing an energy management system according to ISO 50001, the Power Monitor is one of the modules necessary to meet the requirements of recording, displaying and analysing power flows.Technical data: Input data: measurement variable: active, reactive, apparent power Recording of frequencies of up to 99.99 Hz and temperatures of up to 100°CMeasurement variable: AC sine (50/60 Hz) designationInput: voltage measurement inputs V1, V2, V3Input voltage range: 0 VAC - 500 VAC (phase/phase) Input voltage range: 0 VAC - 300 VAC (phase/neutral conductor) Accuracy: 0.5% input current range: via external converters, input current: 8000 A (primary), input current: 5 A (secondary) Response threshold of rated measurement range value: 1 mA Power-measurement range: 0- 9999999.9 kWPower-measurement range: 0- 9999999.9 kvarPower-measurement range: 0- 9999999.9 kVA Accuracy: 1% Interface: RS-485 Type of connection: screw terminals General data: width: 96 mm, height: 96 mmDisplay: LCD display, backlit displaySupply voltage range: 85- 264 VAC Rated power consumption: 5 VA, protection degree: IP51 (front), IP20 (rear) Mains type: 3-phase (3 or 4 conductors), 2-phase (2 conductors) and 1-phase (1 conductor), colour: black, conformity: CE-compliantRated insulation voltage: 300 VAC (EN 61010-1)Overvoltage category: II, ambient temperature (operational): -25°C to 55°C, ambient temperature (storage/transport): -25°C to 70°C Max. perm. humidity (operation): 85%, height above sea level < 2000 mConnection data: flexible conductor cross-section min.: 0.5 mm², flexible conductor cross-section max.: 2.5 mm², rigid conductor cross-section min.: 0.2 mm², rigid conductor cross-section max.: 4 mm², type of connection: screw connectionOrdering details: product: Weidm¼ller interface, type: Power Monitor, item no.: 1423550000
- Short specification
- Measuring device for optimising energy requirements
Measuring Current Input
- Current-measuring channels
- 3
- Measuring accuracy for current
- 0.5 %
- Rated current
- 1 / 5 A
- Residual current measuring
- No
Classifications
- ETIM 6.0
- EC002301
- ETIM 7.0
- EC002301
- EClass 9.0
- 27-14-23-30
- EClass 9.1
- 27-21-03-01
- EClass 10.0
- 27-14-23-30
- UNSPSC
- 39-12-15-35
Measuring Voltage Input
- Four-wire system
- Yes
- Measurement range, voltage L-L, AC
- 0¦500 V
- Measurement range, voltage L-N, AC
- 0¦250 V (1P3W), 0¦289 V (3P4W)
- Measuring accuracy for voltage
- 1 %
- Three-wire system
- Yes
Technical Data
- Standards
- IEC 61010-1
- Measurement range, voltage L-N, AC
- 0¦250 V (1P3W), 0¦289 V (3P4W)
- Measurement range, voltage L-L, AC
- 0¦500 V
- Surge voltage category
- II
- Voltage supply
- 100¦240 V AC, 100...300 V DC
- Supply voltage
- 230 V
- Three-wire system
- Yes
- Four-wire system
- Yes
- Sampling frequency 50/60 Hz
- 1,024 kHz
- Measurement result per second
- 100,000
- Residual current measuring
- No
- Measuring accuracy for voltage
- 1 %
- Measuring accuracy for current
- 0.5 %
- Measurement accuracy for active energy (kWh, ¦/5 A)
- 1% for the calculated values
- Current-measuring channels
- 3
- Clock
- Yes
Insulation Coordination
- Pollution severity
- 2
- Surge voltage category
- II
Temperatures
- Humidity
- 35 % to 85 % relative humidity level
- Operating temperature, max.
- 55 °C
- Operating temperature, min.
- -25 °C
- Storage temperature, max.
- 70 °C
- Storage temperature, min.
- -25 °C
- Operating temperature
- -25°C...55°C
- Storage temperature
- -25°C...70°C