Additional Information
- Part Number
- 1319280000
Monitoring Circuit
- Connection designation
- S11, S12, S21, S22
- Input
- 2, each externally bridgeable
- Operating voltage
- 22 V DC, from internal power supply
Output (Release Circuit)
- Connection designation
- 13, 14, 23, 24
- Contact design
- 2 NO positively-driven (EN 50205 type B)
- Contact base material
- AgSnO
- Switching voltage AC, max.
- 250 V
- Max. permissible switching current
- 6 A
- Max. switching current, external fuse
- 5 A
- Max. switching capacity
- 2000 VA
- External back-up fuse
- 5 A time lag
- Turn-on time
- 55 ms (C1/C2 bridged, switched via A1/A2), 30 ms (opening/closing of monitoring circuit)
- Turn-off time
- 20 ms (C1/C2 bridged, switched via A1/A2), 15 ms (opening/closing of monitoring circuit)
- Min. switching capacity
- 10 mA @ 12 V
General Data
- Rail
- TS 35
- Colour
- black, yellow
Output (Safety Circuit)
- External back-up fuse
- 5 A time lag
Starting Circuit
- Anschlussbezeichnung
- S33, S34, S35
- Operating voltage
- 22 V DC, from internal power supply
- Function
- falling edge (button via S33/S34), rising edge (permanent bridge via S33/S35)
Feedback Output
- Connection designation
- 31, 32
- Contact design
- 1 NC positively-driven (EN 50205 type B)
- Switching voltage AC, max.
- 250 V
- Max. switching current.
- 1 A
Approvals
- Approvals
- CE, EAC, FUSAFETY
- ROHS
- Conform
Dimensions And Weights
- Width
- 22.5 mm
- Width (inches)
- 0.886 inch
- Height
- 119.6 mm
- Height (inches)
- 4.709 inch
- Depth
- 114.1 mm
- Depth (inches)
- 4.492 inch
- Net weight
- 292 g
Connection Data
- Wire connection method
- Screw connection
- Tightening torque, min.
- 0.4 Nm
- Tightening torque, max.
- 0.6 Nm
- Clamping range, rated connection
- 1.5 mm²
- Clamping range, min.
- 0.13 mm²
- Clamping range, max.
- 2.5 mm²
- Wire connection cross section AWG, min.
- AWG 26
- Wire connection cross section AWG, max.
- AWG 12
- Wire cross-section, solid, min.
- 0.2 mm2
- Wire cross-section, solid, max.
- 2.5 mm2
- Wire connection cross-section, finely stranded, min.
- 0.2 mm2
- Wire connection cross section, finely stranded, max.
- 2.5 mm2
- Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min.
- 0.2 mm2
- Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max.
- 2.5 mm²
- Conductor cross-section, flexible, AEH (DIN 46228-1), min.
- 0.2 mm2
- Conductor cross-section, flexible, AEH (DIN 46228-1), max.
- 2.5 mm2
- Twin wire-end ferrules, min.
- 0.5 mm2
- Twin wire-end ferrules, max.
- 1.5 mm2
- Blade size
- size PH0
Input (Power Supply)
- Connection designation
- A1, A2, C1, C2
- Rated control voltage
- 24 V DC ±15 %, 24 VDC +15% / -10% during auto-start
- Current consumption
- 55 mA (release circuit enabled), 6 mA (release circuit not enabled)
- Guaranteed current consumption at 24 V DC -10%
- 35 mA
- Inrush current
- 750 mA / 5 ms (for starting with S33/S34 (start circuit)), 2 A / 20 ms (for starting with A1/A2 (autostart))
- Response time
- with bridge via C1/C2: typ. 50 ms, without bridge via C1/C2: typ. 20 ms
- Status display
- LED green: supply, Yellow LED: signal
- Protective circuit
- Reverse polarity protection, Free-wheeling diode
- Short-circuit detection
- Yes, max. 4 s up to disconnection (thermistor)
Safety-Related Basic Specifications
- Device type
- A
- Hardware fault tolerance (HFT)
- 1
- T
- 12 Years
- Safety category
- SIL 3
- Safety standard
- DIN EN 61508, EN ISO 13849-1 (PLe)
Classifications
- ETIM 6.0
- EC001449
- ETIM 7.0
- EC001449
- EClass 9.0
- 27-37-18-19
- EClass 9.1
- 27-37-18-19
- EClass 10.0
- 27-37-18-19
Environmental Product Compliance
- REACH SVHC
- Lead 7439-92-1
Insulation Coordination
- Rated voltage
- 300 V
- Surge voltage category
- III
- Pollution severity
- 2
- Protection degree
- IP20
- Dielectric strength, Input/Output
- 4 kVeff / 1 min
- Creepage and clearance distance input – output
- ? 5.5 mm
- Dielectric strength output – output
- 4 kVeff / 1 min
- Creepage and clearance distance output – output
- ? 5.5 mm
- Dielectric strength to mounting rail
- 4 kVeff / 1 Min.
- Impulse withstand voltage
- 6 kV (1.2/50 µs)
Temperatures
- Humidity
- 40 °C / 93 % rel. humidity, no condensation
- Operating temperature, max.
- 55 °C
- Operating temperature, min.
- -25 °C
- Storage temperature, max.
- 85 °C
- Storage temperature, min.
- -40 °C
- Operating temperature
- -25 °C...55 °C
- Storage temperature
- -40 °C...85 °C
Further Details Of Approvals / Standards
- Standards
- EN 50178, EN 61000, EN 61326-3-2, EN ISO 13849-1 (PLe)
- Equipment for furnaces
- EN 50156