Additional Information
- Part Number
- 750-489
- UPC
- 4055143948029
- Tariff Code
- 85389099990
- ETIM
- Group Code : EG000024
- Group Description : PLC's
- Class Description : Fieldbus, decentr. periphery - analogue I/O module
- Class Code : EC001596
- Version : 7
Environmental Requirements
- Ambient temperature (operation)
- 0 ¦ +55°C
- Ambient temperature (storage)
- -25 ¦ +85°C
- Protection type
- IP20
- Pollution degree
- 2 per IEC 61131-2
- Operating altitude
- 0 ¦ 2000 m / 0 ¦ 6562 ft
- Mounting position
- Horizontal (standing/lying); vertical
- Relative humidity (without condensation)
- 95 %
- Vibration resistance
- 4g per IEC 60068-2-6
- Shock resistance
- 15g per IEC 60068-2-27
- EMC immunity to interference
- Per EN 61000-6-2, marine applications
- EMC emission of interference
- Per EN 61000-6-3, marine applications
- Exposure to pollutants
- Per IEC 60068-2-42 and IEC 60068-2-43
Connection Data
- Connection technology: inputs/outputs
- 16 x CAGE CLAMP®
- Connection type 1
- Inputs/outputs
- Solid conductor
- 0.08 ¦ 2.5 mm² / 28 ¦ 14 AWG
- Fine-stranded conductor
- 0.08 ¦ 2.5 mm² / 28 ¦ 14 AWG
- Strip length
- 8 ¦ 9 mm / 0.31 ¦ 0.35 inches
Physical Data
- Width
- 24 mm / 0.945 inches
- Height
- 100 mm / 3.937 inches
- Depth
- 67.8 mm / 2.669 inches
- Depth from upper-edge of DIN-rail
- 60.6 mm / 2.386 inches
Material Data
- Housing material
- Polycarbonate; polyamide 6.6
- Fire load
- 2.036 MJ
- Weight
- 99.300 g
- Conformity marking
- CE
Technical Data
- Number of analog inputs
- 4
- Total number of channels (module)
- 4
- Signal type
- Potentiometer positions || Thermocouple || Resistive temperature device || Resistors || MV encoder
- Signal type (configurable)
- Yes
- Sensor connection
- 4 x (2-wire); RTD/R: 3-wire; 4-wire
- Data width
- 4 x 16-bit data; 4 x 8-bit control/status (optional)
- Resolution (over entire range)
- 0.1 K of full scale value; 0.01 K of full scale value (restricted to -50°C ¦ +150°C)
- Conversion time
- ¥10 ms/2 wires (per channel)*; ¥20 ms/3 wires, 4 wires (per channel)*; *for RTD/R; TC/U conversion time depends on module setting
- Measurement error (25°C)
- In delivery state: ±0.2 % of the upper-range value (value achieved during calibration in operating environment 0 ¤ TA ¤ 55°C); After user calibration: ±0.05 % of the upper-range value (only valid in the thermally stable operating state)
- Temperature coefficient
- ±0.001 %/K of the upper-range value
- Intrinsic safety Ex i
- Yes
- Measurement range
- Resistive temperature devices: Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Ni1000-TK5000; Resistors: 250 ©, 500 ©, 1 k©, 2 k©, 4 k©, PTC; Potentiometer setting: 0 ¦ 100 %; Thermocouples: Type B (+250 ¦ +1,820°C); Type C (0 ¦ +2,315°C); Type E (-200 ¦ +1,000°C); Type J (-210 ¦ +1,200°C); Type K (-200 ¦ +1,372°C); Type N (-200 ¦ +1,300°C); Type R, S (-50 ¦ +1,768°C); Type T (-200 ¦ +400°C); mV sensors: ±30 mV; ±60 mV; ±120 mV; ±250 mV; ±500 mV; ±1,000 mV; ±2,000 mV; Thermistor: PTC; Resistor bridges (strain gauges): Uref: 2.4 V; Ud: ±15 mV, ±30 mV, ±60 mV
- Cold junction compensation
- Integrated
- Configuration options
- WAGO-I/O-CHECK || CODESYS Library || e!COCKPIT
- Supply voltage (system)
- 5 VDC; via data contacts
- Current consumption (5 V system supply)
- 60 mA
- Supply voltage (field)
- 24 VDC; (Ex i power supply: UO = max. 27.3 V); via power jumper contacts (power supply via blade contact; transmission via spring contact)
- Current consumption, field supply (module with no external load)
- 120 mA
- Power loss Pl
- 1.6 W
- Isolation
- Per EN/IEC 60079-11: 300 VAC system/supply; per EN/UL 61010-2-201: 1200 VDC system/supply/channel
- Indicators
- LED (A, C, E, G) green: Function AI 1 ¦ AI 4; LED (B, D, F, H) red: Error AI 1 ¦ AI 4
- Number of incoming power jumper contacts
- 2
- Number of outgoing power jumper contacts
- 2
- Marking
- ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I
Mechanical Data
- Mounting type
- DIN-35 rail
Specifications
- Product Group Code
- 0015
Commercial Data
- Packaging type
- Box
- Country of origin
- DE
- GTIN
- 4055143948029
- Customs tariff number
- 85389099990
Notes
- Note
- The analog input module must only be operated via 24 VDC Ex i!General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals!
Explosion Protection
- Ex standard
- EN IEC 60079-0, -7, -11
- Safety-relevant data (circuit)
- Uo = 4 V; Io = 13.46 mA; Po = 13.46 mW; linear characteristic curve
- Reactances Ex ia IIC
- Lo = 0.19 H; Co = 100 µF
- Reactances Ex ia IIB
- Lo = 0.78 H; Co = 1000 µF
- Reactances Ex ia IIA
- Lo = 1.57 H; Co = 1000 ¼F
- Reactances Ex ia I
- Lo = 2.57 H; Co = 1000 µF
- Reactances (note)
- Reactances, if the internal inductance Li or capacitance Ci (without cable) of the connected device is ¤1 % of the specified values.