Additional Information
- Part Number
- 750-487/003-000
- UPC
- 4045454961893
- Tariff Code
- 85389099990
- ETIM
- Group Code : EG000024
- Group Description : PLC's
- Class Description : Fieldbus, decentr. periphery - analogue I/O module
- Class Code : EC001596
- Version : 7
Environmental Requirements
- Ambient temperature (operation)
- 0 … +55°C
- Ambient temperature (storage)
- -25 … +85°C
- Protection type
- IP20
- Pollution degree
- 2 per IEC 61131-2
- Operating altitude
- 0 … 2000 m / 0 … 6562 ft
- Mounting position
- Horizontal (standing/lying); vertical
- Relative humidity (without condensation)
- 95 %
- Vibration resistance
- 4g per IEC 60068-2-6
- Shock resistance
- 15g per IEC 60068-2-27
- EMC immunity to interference
- Per EN 61000-6-2, marine applications
- EMC emission of interference
- Per EN 61000-6-3, marine applications
- Exposure to pollutants
- Per IEC 60068-2-42 and IEC 60068-2-43
- Permissible H2S contaminant concentration at a relative humidity 75 %
- 10 ppm
- Permissible SO2 contaminant concentration at a relative humidity 75 %
- 25 ppm
Connection Data
- Connection technology: inputs/outputs
- 16 x CAGE CLAMP®
- Connection type 1
- Inputs/outputs
- Solid conductor
- 0.08 … 2.5 mm² / 28 … 14 AWG
- Fine-stranded conductor
- 0.08 … 2.5 mm² / 28 … 14 AWG
- Strip length
- 8 … 9 mm / 0.31 … 0.35 inches
Physical Data
- Width
- 24 mm / 0.945 inches
- Height
- 100 mm / 3.937 inches
- Depth
- 67.8 mm / 2.669 inches
- Depth from upper-edge of DIN-rail
- 60.6 mm / 2.386 inches
Material Data
- Housing material
- Polycarbonate; polyamide 6.6
- Fire load
- 2.063 MJ
- Weight
- 90.500 g
- Conformity marking
- CE
Technical Data
- Number of analog inputs
- 2
- Total number of channels (module)
- 2
- Signal type
- Thermocouple || Low voltages
- Signal type (configurable)
- Yes
- Sensor connection
- 2 x (2-wire)
- Power consumption Pmax.
- 0.3 W (max.)
- Data width
- 2 x 16-bit data; 2 x 8-bit control/status (optional)
- Internal resistance
- 1000 k?
- Resolution (over entire range)
- 0.1°C or 0.01 mV for voltage measurement
- Conversion time (typ.)
- 320 ms
- Conversion time
- ? 320 ms (both channels)
- Measurement error (25°C)
- < ±6 K (voltage input < ±2 K; cold junction compensation < ±4 K)
- Temperature coefficient
- < ± 0.2 K / K of the largest output area (type K)
- Intrinsic safety Ex i
- Yes
- Sensor types
- Thermocouple K; Configurable: J, B, E, L, N, R, S, T, U, C; Voltage sensor: ±30 mV, ±60 mV, ±120 mV
- Temperature range
- Type-dependent from ?100 to +1,800°C
- Measurement range
- Thermocouples: Type B: +600 … +1.800°C; Type E: –100 … +1.000°C; Type J: –100 … +1.200°C; Type K: –100 … +1.370°C* *(default setting); Type L: -100 … +900°C; Type N: –100 … +1.300°C; Type R: 0 … +1.700°C; Type S: –50 … +1.700°C; Type T: –100 … +400°C; Type U: -25 … +600°C; Voltage sensors: MB1: ±30 mV; MB2: ±60 mV; MB3: ±120 mV
- Cold junction compensation
- Internal; at each pair of terminal blocks
- Configuration options
- WAGO-I/O-CHECK || CODESYS Library || e!COCKPIT
- Supply voltage (system)
- 5 VDC; via data contacts
- Current consumption (5 V system supply)
- 13.5 mA
- Supply voltage (field)
- 24 VDC; (Ex i power supply: UO = max. 27.3 V); via power jumper contacts (power supply via blade contact; transmission via spring contact)
- Current consumption, field supply (module with no external load)
- 8.5 mA
- Power loss Pl
- 0.3 W (max.)
- Isolation
- 300 VAC system/field
- Indicators
- LED (A, E) green: Function AI 1, AI 2; LED (B, F) red: Error AI 1, AI 2
- Number of incoming power jumper contacts
- 2
- Number of outgoing power jumper contacts
- 2
- Marking
- ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I
Mechanical Data
- Mounting type
- DIN-35 rail
Specifications
- Product Group Code
- 0015
Commercial Data
- Packaging type
- Box
- Country of origin
- DE
- GTIN
- 4045454961893
- Customs tariff number
- 85389099990
Notes
- Note
- The analog input module must only be operated via 24 VDC Ex i!General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals!
Explosion Protection
- Ex standard
- EN IEC 60079-0, -7, -11
- Safety-relevant data (circuit)
- Uo = 14.4 V; Io = 29.1 mA; Po = 52.4 mW; linear characteristic curve
- Reactances Ex ia IIC
- Lo = 52 mH; Co = 650 nF
- Reactances Ex ia IIB
- Lo = 100 mH; Co = 4.0 µF
- Reactances Ex ia IIA
- Lo = 300 mH; Co = 15.8 ?F
- Reactances Ex ia I
- Lo = 400 mH; Co = 17.9 µF
- Reactances (note)
- Reactances without accounting for the concurrence of capacitance (Co) and inductance (Lo)