Additional Information
- Part Number
- SU12000RT4U
- UPC
- 037332154897
Overview
- UPC Code
- 037332154897
- UPS Type
- On-Line
Output
- Output Volt Amp Capacity (VA)
- 12000
- Output kVA Capacity (kVA)
- 12
- Output Watt Capacity (Watts)
- 8400
- Output kW Capacity (kW)
- 8.4
- Power Factor
- 0.7
- Crest Factor
- 3:1
- Nominal Voltage Details
- 240/120V or 208/120V split phase output
- Frequency Compatibility
- 60 Hz
- Output Voltage Regulation (Line Mode)
- +/- 3%
- Output Voltage Regulation (Economy Line Mode)
- +/- 10%
- Output Voltage Regulation (Battery Mode)
- +/- 3%
- Output Receptacle Details
- Supports North American 208/120V or 240/120V split-phase hardwire output (L1, L2, N, G)
- Output Circuit Breakers
- 20A branch rated double pole breakers (x3) protect 2 C19 and 1 5-15/20R outlets each, 30A branch rated double pole breakers (x2) protect 1 L6-30R outlet each, 20A single pole breakers (x2) protect one 5-15/20R outlet each
- Output AC Waveform (AC Mode)
- Pure Sine wave
- Output AC Waveform (Battery Mode)
- Pure Sine wave
- Output Capacity Details
- 12,000VA, 8400W (240V) / 10,395VA, 8400W (208V); Supports up to 105% load continuously in double conversion mode, 106 to 125% for 3 minutes, 126 to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support equipment directly from mains power; Double conversion mode is automatically restored as the overload is cleared
- Nominal Output Voltage(s) Supported
- 120V; 208V; 240V
- Output Receptacles
- (5) 5-15/20R; (2) L6-30R; (6) C19; Hardwire
- Individually Controllable Load Banks
- No
Input
- Rated input current (Maximum Load)
- 50A
- Nominal Input Voltage(s) Supported
- 120/208V (Split phase L1,L2,N,G); 120/240V (Split phase L1,L2,N,G)
- UPS Input Connection Type
- Hardwire
- UPS Input Connection Description
- 4 wire split-phase input (L1, L2, N, G)
- Recommended Electrical Service
- 50A 208/240-120 Split Phase (L1, L2, N, G); 6 AWG wiring recommended
- Input Phase
- Single-Phase
Battery
- Full Load Runtime (min.)
- 7 min. (8400w)
- Half Load Runtime (min.)
- 20 min. (4200w)
- Expandable Battery Runtime
- Supports extended runtime with optional external battery packs
- External Battery Pack Compatibility
- BP192V18-4U
- DC System Voltage (VDC)
- 192
- Battery Recharge Rate (Included Batteries)
- Less than 6 hours from 10% to 80% (typical, full load discharge)
- Battery Replacement Description
- Hot-swappable, user replaceable batteries
- Expandable Runtime
- Yes
Voltage Regulation
- Voltage Regulation Description
- +/-3% output voltage regulation in online, double-conversion mode
- Overvoltage Correction
- Corrects overvoltages to 140 (measured L1-N : L2-N)
- Undervoltage Correction
- Corrects undervoltages to 65V (measured L1-N : L2-N)
User Interface, Alerts & Controls
- Front Panel LCD Display
- Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats
- Switches
- 2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and execute scrolling LCD functions; bundled PDU includes bypass switch to enable hot-swap UPS power module replacement
- Alarm Cancel Operation
- Alarm cancel switch
- Audible Alarm
- Unique audible alarms for all major UPS, environmental and power conditions (see manual)
- LED Indicators
- 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options
Surge / Noise Suppression
- UPS AC Suppression Joule Rating
- 3620
- UPS AC Suppression Response Time
- Instantaneous
- EMI / RFI AC Noise Suppression
- Yes
Physical
- Cooling Method
- Fan
- Included Battery Pack Dimensions (hwd / in.)
- 7 x 17.5 x 27.8
- Included Battery Pack Weight (lbs.)
- 239
- Included Mounting Accessory Description
- 2 sets of adjustable 4 post rack rails included
- Installation Form Factors Supported with Included Accessories
- 4 post 19 inch rackmount
- Installation Form Factors Supported with Optional Accessories
- 2 post rackmount (2POSTRMKITHD); Tower (2-9USTAND)
- Maximum Device Depth (in.)
- 34
- Minimum Required Rack Depth (inches)
- 40
- Optional Mounting Accessory Notes
- 2 sets of 2POSTRMKITHD required for 2 post rackmount installation
- Primary Form Factor
- Rackmount
- Primary UPS Depth (mm)
- 706
- Primary UPS Height (mm)
- 178
- Primary UPS Width (mm)
- 445
- Rack Height
- 8U
- Shipping Dimensions (hwd / in.)
- 37.00 x 24.00 x 33.50
- Shipping Weight (lbs.)
- 448.80
- UPS Dimensions Details
- Includes 4U battery pack, 4U UPS/power module and detachable bypass PDU; MAXIMUM DEVICE DEPTH specification refers to the whole UPS installed depth with bypass PDU installed
- UPS Housing Material
- Steel
- UPS Power Module Dimensions (hwd, in.)
- 7 x 17.5 x 27.8
- UPS Power Module Weight (kg)
- 39.01
- UPS Power Module Weight (lbs.)
- 86
Environmental
- Operating Temperature Range
- +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.
- Storage Temperature Range
- +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.
- Relative Humidity
- 0 to 95%, non-condensing
- AC Mode BTU / Hr. (Full Load)
- 4286
- AC Economy Mode BTU / Hr. (Full Load)
- 1829
- Battery Mode BTU / Hr. (Full Load)
- 3187
- AC Mode Efficiency Rating (100% Load)
- 87%
- AC Economy Mode Efficiency Rating (100% Load)
- 94%
- Operating Elevation (ft.)
- 0-3000m (0 to 10,000 ft.)
- Audible Noise
- 60 dBA at front side 1 meter
- Operating Elevation (m)
- 0-3000 m
Communications
- Network Management Cards
- SNMPWEBCARD; WEBCARDLX; MODBUSCARD; RELAYIOCARD
- Network Monitoring Port Description
- RS232 and contact closure communications are supported on one DB9 port
- PowerAlert Software
- For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
- Communications Cable
- USB and DB9 cabling included
- Communications Interface
- USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Line / Battery Transfer
- Transfer Time
- No transfer time (0 ms.) in online, double-conversion mode
- Transfer Time (Economy Mode)
- 2 milliseconds typical in optional economy mode
- Low Voltage Transfer to Battery Power (Setpoint)
- 65V (L1-N:L2-N)
- High Voltage Transfer to Battery Power (Setpoint)
- 140V (L1-N:L2-N)
Special Features
- Cold Start (Startup in Battery Mode During a Power Failure)
- Cold-start operation supported
- High Availability UPS Features
- Automatic inverter bypass; Hot swappable batteries; Hot swappable UPS power module; Manual bypass switch
- Green Energy-Saving Features
- High efficiency economy mode operation; Schedulable daily hours of economy mode operation
Certifications
- UPS Certifications
- Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
Warranty
- Product Warranty Period (Worldwide)
- 2-year limited warranty
- Connected Equipment Insurance (U.S., Canada & Puerto Rico)
- $250,000 Ultimate Lifetime Insurance