Additional Information
- Part Number
- SMX5000XLRT3U
- UPC
- 037332121455
Overview
- UPC Code
- 037332121455
- UPS Type
- Line-Interactive
Output
- Output Volt Amp Capacity (VA)
- 5000
- Output kVA Capacity (kVA)
- 5
- Output Watt Capacity (Watts)
- 3750
- Output kW Capacity (kW)
- 3.75
- Power Factor
- 0.75
- Nominal Voltage Details
- 230v nominal inverter output voltage
- Frequency Compatibility
- 50 / 60 Hz
- Frequency Compatibility Details
- Automatic frequency selection
- Output Voltage Regulation (Line Mode)
- -17%, +8%
- Output Voltage Regulation (Battery Mode)
- +/- 5%
- Included Output Power Cables
- Includes 3 C13 to C14 output power cables
- Output Circuit Breakers
- 15A (x3) breaker supports 1 C19 outlet each, 10A (x2) breaker supports 4 C13 outlets each
- Output AC Waveform (AC Mode)
- Sine wave
- Output AC Waveform (Battery Mode)
- Pure Sine wave
- Nominal Output Voltage(s) Supported
- 220V; 230V; 240V
- Output Receptacles
- (8) C13; (3) C19
- Individually Controllable Load Banks
- No
Input
- Rated input current (Maximum Load)
- 27A
- Nominal Input Voltage(s) Supported
- 230V AC
- UPS Input Connection Type
- Hardwire
- UPS Input Connection Description
- Hardwire input supports International 230V input (L, N, PE)
- Input Phase
- Single-Phase
Battery
- Full Load Runtime (min.)
- 8.5 min. (3750w)
- Half Load Runtime (min.)
- 20 min. (1875w)
- Expandable Battery Runtime
- Extended runtime supported via optional external battery packs
- External Battery Pack Compatibility
- BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V27-2US (multi-pack compatible)
- DC System Voltage (VDC)
- 48
- Battery Recharge Rate (Included Batteries)
- Less than 4 hours from 10% to 90% (typical, full load discharge)
- Internal UPS Replacement Battery Cartridge
- RBC94-3U (quantity 3)
- Battery Access
- Front panel battery access door
- Battery Replacement Description
- Hot-swappable, user replaceable batteries
- Expandable Runtime
- Yes
Voltage Regulation
- Voltage Regulation Description
- Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 170 to 282
- Overvoltage Correction
- Input voltages between 245 and 282 are reduced by 12%
- Undervoltage Correction
- Input voltages between 170 and 199 are boosted by 12%
User Interface, Alerts & Controls
- Switches
- 2 Switches control off/on power status and alarm-cancel/self-test operation
- Alarm Cancel Operation
- Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status
- Audible Alarm
- Audible alarm indicates power-failure, overload and low-battery conditions
- LED Indicators
- 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Surge / Noise Suppression
- UPS AC Suppression Joule Rating
- 480
- UPS AC Suppression Response Time
- Instantaneous
- EMI / RFI AC Noise Suppression
- Yes
Physical
- Cooling Method
- Fans
- Installation Form Factors Supported with Included Accessories
- 4 post 19 inch rackmount
- Installation Form Factors Supported with Optional Accessories
- 2 post rackmount ( 2POSTRMKITHD ); Tower ( 2-9USTAND )
- Minimum Required Rack Depth with External Battery Pack (cm)
- 81
- Minimum Required Rack Depth with External Battery Pack (in.)
- 32
- Minimum Required Rack Depth without External Battery Pack (cm)
- 72
- Minimum Required Rack Depth without External Battery Pack (in.)
- 28.5
- Primary Form Factor
- Rackmount
- Primary UPS Depth (mm)
- 635
- Primary UPS Height (mm)
- 132
- Primary UPS Width (mm)
- 445
- Rack Height
- 3U
- Shipping Dimensions (hwd / in.)
- 11.25 x 22.52 x 31.50
- Shipping Weight (lbs.)
- 182.00
- UPS Housing Material
- Steel
- UPS Power Module Dimensions (hwd, in.)
- 5.2 x 17.5 x 25
- UPS Power Module Weight (kg)
- 64.86
- UPS Power Module Weight (lbs.)
- 143
Environmental
- Operating Temperature Range
- +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
- Storage Temperature Range
- +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
- Relative Humidity
- 0 to 95%, non-condensing
- AC Mode BTU / Hr. (Full Load)
- 271
- Battery Mode BTU / Hr. (Full Load)
- 1267
- AC Mode Efficiency Rating (100% Load)
- 98%
- Audible Noise
- 45 dBA maximum, front side 1m
Communications
- Network Management Cards
- SNMPWEBCARD ; TLNETCARD ; WEBCARDLX
- Network Monitoring Port Description
- Supports detailed monitoring of UPS and site power conditions
- PowerAlert Software
- For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
- Communications Cable
- USB and DB9 cabling included
- WatchDog Compatibility
- Supports Watchdog application, OS and hard-reboot restart options for remote applications
- Communications Interface
- USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Line / Battery Transfer
- Transfer Time
- 7 ms (AC to Battery); 1 ms (Battery to AC) typical
- Low Voltage Transfer to Battery Power (Setpoint)
- 170
- High Voltage Transfer to Battery Power (Setpoint)
- 282
Special Features
- Grounding Lug
- Back panel grounding lug
- Cold Start (Startup in Battery Mode During a Power Failure)
- Cold-start operation supported
- High Availability UPS Features
- Hot swappable batteries
- Green Energy-Saving Features
- Greater than 95% efficiency - GREEN UPS
Certifications
- UPS Certifications
- CE
- UPS Certification Details
- Class A (EMI)
Warranty
- Product Warranty Period (International)
- 2-year limited warranty