Additional Information
- Part Number
- SMX1500XLRT2U
- UPC
- 037332119216
Overview
- UPC Code
- 037332119216
- UPS Type
- Line-Interactive
Output
- Output Volt Amp Capacity (VA)
- 1500
- Output kVA Capacity (kVA)
- 1.5
- Output Watt Capacity (Watts)
- 1350
- Output kW Capacity (kW)
- 1.35
- Power Factor
- 0.9
- Nominal Voltage Details
- 230V nominal output in battery mode
- Frequency Compatibility
- 50 / 60 Hz
- Frequency Compatibility Details
- Automatic frequency selection
- Output Voltage Regulation (Line Mode)
- +6% / -15%
- Output Voltage Regulation (Battery Mode)
- +/- 5%
- Included Output Power Cables
- Set of 2 C13 to C14 power cables included
- Load Management Receptacles
- Two switchable two-outlet C13 load banks
- Output AC Waveform (AC Mode)
- Sine wave
- Output AC Waveform (Battery Mode)
- Pure Sine wave
- Output Capacity Details
- Output is reduced to 1200W maximum when used with external battery packs
- Nominal Output Voltage(s) Supported
- 220V; 230V; 240V
- Output Receptacles
- (8) C13
- Individually Controllable Load Banks
- Yes
Input
- Rated input current (Maximum Load)
- 6.9A
- Nominal Input Voltage(s) Supported
- 230V AC
- UPS Input Connection Type
- C14 inlet
- UPS Input Connection Description
- IEC320-C14 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles
- Input Circuit Breakers
- 10A
- Input Phase
- Single-Phase
Battery
- Full Load Runtime (min.)
- 4.9 min. (1350w)
- Half Load Runtime (min.)
- 13.6 min. (675w)
- Expandable Battery Runtime
- Extended runtime supported via optional external battery packs
- External Battery Pack Compatibility
- BP36V15-2U (limit 1); BP36V42-3U (multi-pack compatible); BP36V27 -2US (multi-pack compatible)
- DC System Voltage (VDC)
- 36
- Battery Recharge Rate (Included Batteries)
- Less than 4.5 hours from 10% to 90% (typical, full load discharge)
- Internal UPS Replacement Battery Cartridge
- RBC93-2U
- Battery Access
- Front panel battery access door
- Battery Replacement Description
- Hot-swappable, user replaceable batteries
- Expandable Runtime
- Yes
Voltage Regulation
- Voltage Regulation Description
- Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 158 to 278
- Overvoltage Correction
- Input voltages between 244 and 278 are reduced by 12%
- Undervoltage Correction
- Input voltages between 182 and 206 are boosted by 12%
- Severe Undervoltage Correction
- Input voltages between 158 and 182 are boosted by 24%
User Interface, Alerts & Controls
- Front Panel LCD Display
- Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
- Switches
- 3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
- Alarm Cancel Operation
- Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
- Audible Alarm
- Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
Surge / Noise Suppression
- UPS AC Suppression Joule Rating
- 350
- UPS AC Suppression Response Time
- Instantaneous
- EMI / RFI AC Noise Suppression
- Yes
Physical
- Cooling Method
- Fan
- Included Mounting Accessory Description
- Included 4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to 914mm)
- Installation Form Factors Supported with Included Accessories
- 4 post 19 inch rackmount
- Installation Form Factors Supported with Optional Accessories
- 2 post rackmount ( 2POSTRMKITWM ); 2-4 post front rail rackmount ( UPSHDEARKIT ); 4 post rackmount short-depth ( 4POSTRAILKITWM ); Tower ( 2-9USTAND ); Wallmount ( 2POSTRMKITWM )
- Minimum Required Rack Depth with External Battery Pack (cm)
- 51
- Minimum Required Rack Depth with External Battery Pack (in.)
- 20
- Minimum Required Rack Depth without External Battery Pack (cm)
- 40
- Minimum Required Rack Depth without External Battery Pack (in.)
- 15.75
- Optional Mounting Accessory Notes
- Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation; 4POSTRAILKITWM enables installation in 4-post short-depth racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post racks using front vertical rails only, without rear support
- Primary Form Factor
- Rackmount
- Primary UPS Depth (mm)
- 343
- Primary UPS Height (mm)
- 89
- Primary UPS Width (mm)
- 442
- Rack Height
- 2U
- Shipping Dimensions (hwd / in.)
- 8.80 x 19.90 x 23.30
- Shipping Weight (lbs.)
- 56.70
- UPS Housing Material
- Steel
- UPS Power Module Dimensions (hwd, in.)
- 3.5 x 17.4 x 13.5
- UPS Power Module Weight (kg)
- 19.55
- UPS Power Module Weight (lbs.)
- 43.1
Environmental
- Operating Temperature Range
- +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
- Storage Temperature Range
- +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
- Relative Humidity
- 0 to 95%, non-condensing
- AC Mode BTU / Hr. (Full Load)
- 139
- Battery Mode BTU / Hr. (Full Load)
- 689
- AC Mode Efficiency Rating (100% Load)
- 97%
- Audible Noise
- 45 dBA maximum, front side 1m
Communications
- Network Management Cards
- SNMPWEBCARD ; TLNETCARD ; WEBCARDLX ; RELAYIOCARD
- Network Monitoring Port Description
- Supports detailed monitoring of UPS and site power conditions
- PowerAlert Software
- For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
- Communications Cable
- USB and DB9 cabling included
- WatchDog Compatibility
- Supports Watchdog application, OS and hard-reboot restart options for remote applications
- Communications Interface
- USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Line / Battery Transfer
- Transfer Time
- 6 ms. (AC to DC) / 1 ms. (DC to AC)
- Low Voltage Transfer to Battery Power (Setpoint)
- 158
- High Voltage Transfer to Battery Power (Setpoint)
- 278
Special Features
- Grounding Lug
- Back panel grounding lug
- Cold Start (Startup in Battery Mode During a Power Failure)
- Cold-start operation supported
- High Availability UPS Features
- Hot swappable batteries
- Green Energy-Saving Features
- Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
Certifications
- UPS Certifications
- CE; Tested to GOST (Russia)
- UPS Certification Details
- EN62040-1, 62040-2 (Class A)
Warranty
- Product Warranty Period (Worldwide)
- 2-year limited warranty