Additional Information
- Part Number
- SMART3000SLT
- UPC
- 037332125767
Overview
- UPC Code
- 037332125767
- UPS Type
- Line-Interactive
Output
- Output Volt Amp Capacity (VA)
- 3000
- Output kVA Capacity (kVA)
- 3
- Output Watt Capacity (Watts)
- 2250
- Output kW Capacity (kW)
- 2.25
- Power Factor
- 0.8
- Nominal Voltage Details
- 120v nominal output in battery mode
- Frequency Compatibility
- 60 Hz
- Output Voltage Regulation (Line Mode)
- -18% / +8%
- Output Voltage Regulation (Battery Mode)
- +/- 5%
- Output Circuit Breakers
- 20A branch rated (x2) - each breaker protects 3 5-15/20R outlets, L5-30R is unbreakered
- Output AC Waveform (AC Mode)
- Sine wave
- Output AC Waveform (Battery Mode)
- Pure Sine wave
- Nominal Output Voltage(s) Supported
- 110V; 115V; 120V
- Output Receptacles
- (6) 5-15/20R; (1) L5-30R
- Individually Controllable Load Banks
- No
Input
- Rated input current (Maximum Load)
- 20A
- Nominal Input Voltage(s) Supported
- 120V AC
- UPS Input Connection Type
- L5-30P
- Input Circuit Breakers
- 30A
- UPS Input Cord Length (ft.)
- 10
- Recommended Electrical Service
- 30A 120V
- Input Phase
- Single-Phase
Battery
- Full Load Runtime (min.)
- 3.5 min. (2250w)
- Half Load Runtime (min.)
- 9 min. (1125w)
- DC System Voltage (VDC)
- 48
- Battery Recharge Rate (Included Batteries)
- Less than 4.5 hours from 10% to 90% (typical, full load discharge)
- Internal UPS Replacement Battery Cartridge
- RBC54
- Battery Access
- Battery access door
- Battery Replacement Description
- Hot-swappable, user replaceable batteries
- Expandable Runtime
- No
Voltage Regulation
- Voltage Regulation Description
- Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
- Overvoltage Correction
- Input voltages between 127 and 145 are reduced by 12%
- Undervoltage Correction
- Input voltages between 96 and 108V are boosted by 12%
- Severe Undervoltage Correction
- Input voltages between 83 and 95V are boosted by 24%
User Interface, Alerts & Controls
- Switches
- 2 Switches control off/on power status and alarm-cancel/self-test operation
- Alarm Cancel Operation
- Power-fail alarm can be silenced using alarm-cancel switch
- Audible Alarm
- Audible alarm indicates power failure and overload conditions
- LED Indicators
- 9 LEDs indicate line power, battery power, AVR, overload and replace battery status - with a 3-LED level meter for load and battery charge level
Surge / Noise Suppression
- UPS AC Suppression Joule Rating
- 570
- UPS AC Suppression Response Time
- Instantaneous
- EMI / RFI AC Noise Suppression
- Yes
Physical
- Cooling Method
- Fan
- Primary Form Factor
- Tower
- Primary UPS Depth (mm)
- 318
- Primary UPS Height (mm)
- 267
- Primary UPS Width (mm)
- 226
- Shipping Dimensions (hwd / in.)
- 15.30 x 17.80 x 13.70
- Shipping Weight (lbs.)
- 75.50
- UPS Housing Material
- Steel
- UPS Power Module Dimensions (hwd, in.)
- 10.5 x 8.9 x 12.5
- UPS Power Module Weight (kg)
- 25.85
- UPS Power Module Weight (lbs.)
- 57
Environmental
- Operating Temperature Range
- +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
- Storage Temperature Range
- +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
- Relative Humidity
- 0 to 95%, non-condensing
- AC Mode BTU / Hr. (Full Load)
- 320
- Battery Mode BTU / Hr. (Full Load)
- 1251
- AC Mode Efficiency Rating (100% Load)
- 96%
- Audible Noise
- Audible Noise < 50 dBA at Front Side 1 Meter
Communications
- Network Management Cards
- SNMPWEBCARD ; WEBCARDLX ; RELAYIOCARD
- Network Monitoring Port Description
- Supports detailed monitoring of UPS and site power conditions
- PowerAlert Software
- For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
- Communications Cable
- USB and DB9 cabling included
- WatchDog Compatibility
- Supports Watchdog application, OS and hard-reboot restart options for remote applications
- Communications Interface
- USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Line / Battery Transfer
- Transfer Time
- 2-4 milliseconds
- Low Voltage Transfer to Battery Power (Setpoint)
- 83
- High Voltage Transfer to Battery Power (Setpoint)
- 145
Special Features
- Cold Start (Startup in Battery Mode During a Power Failure)
- Cold-start operation supported
- High Availability UPS Features
- Hot swappable batteries
- Green Energy-Saving Features
- Greater than 95% efficiency - GREEN UPS
Certifications
- UPS Certifications
- Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
Warranty
- Product Warranty Period (Worldwide)
- 2-year warranty, 3 year with registration. Note: Registration is required for 3-year warranty.
- Connected Equipment Insurance (U.S., Canada & Puerto Rico)
- $250,000 Ultimate Lifetime Insurance