Additional Information
- Part Number
- 48290000
- Country of Origin
- France
Environmental Characteristics
- Impact resistance
- Front panel: 5J - casing: 1J (IEC 61010-1 Ed 3.0)
- Maximum operating altitude
- 6560 feet / 2000 m
- Operating temperature
- -10 … +70°C / +14°F … +158°F (IEC 60068-2-1/IEC 60068-2-2)
- PEP ecopassport - ISO 14025
- SOCO-2014-01-v1-fr, SOCO-2014-01-v1-en
- Vibration
- 0.35 mm, 25 Hz, 20 min/axe (IEC 61557-12)
Certificates and Declaration
- Conformity to standard #3
- CEC Compliant
- Conformity to standard #4
- E257746 Vol.X5 Sec.A7
- Proposition 65 California
- WARNING This product can expose you to chemicals including bisphenol A (BPA), which is known to the State of California to cause birth defects or reproductive harm. For more information go to : www.P65Warnings.ca.gov
Environnement
- Relative humidity
- 55°C / 131°F / 97% RH (IEC 60068-2-30)
- Storage temperature
- -25 … +85°C (IEC 60068-2-1/IEC 60068-2-2)
Safety Standard
- UL product category
- PICQ/PICQ7
Electromagnetic Compatibility
- Immunity to conducted disturbances
- 400A/m LEVEL IV
- Immunity to electrical fast transients/bursts
- LEVEL IV
- Immunity to electrostatic discharges on contact
- LEVEL III
- Immunity to electrostatic fields in the air
- LEVEL III
- Immunity to power frequency magnetic fields
- CLASS B
- Immunity to radiated electromagnetic fields
- LEVEL IV
- Surge immunity in common mode
- LEVEL III
Accuracy
- ANSI C12.20
- Class 0.2
General Characteristics
- Display compatibility
- DIRIS D-30
- Webserver compatibility
- WEBVIEW-M
Specifications
- Country of Origin
- France
- Dimensions
- 3 modules wide (54mm)
Communication Characteristics
- Communication Ports
- RS485 output
- Communication Protocols
- Modbus RTU
- Communication speed
- 1200-115200 bauds
- Physical layer
- RS485 2-3 half duplex wires - SELV
- USB port interface
- 1 Type B micro USB; Upgrade and configuration of the module
Pmd
- IEC 61557-12
- Class 0.5 for the global measurement chain
Measurement Characteristics
- Active Energy accuracy
- Class 0.2 ANSI C12.20
- Active Power accuracy
- Class 0.2 ANSI C12.20
- Alarms
- 8 alarms with configurable thresholds (low/high)
- Current measurement type
- AC
- Digital input function
- To be configured in device
- Digital input type
- Optocoupler internal polarisation (12 VDC ± 10 %) or external polarisation (10-30VDC ± 10%)
- External sensors association
- TE Solid Core; TR/iTR split Core; TF Flexible
- Frequency accuracy
- Class 0.02
- Frequency range
- 45-65 Hz
- Frequency rating
- 50/60 Hz
- General measurements
- Metering
- Load type
- To be configured in the module
- Measurement level
- Power Quality Analysis
- Measurement updating period
- Configurable from 200ms to 60s
- Network type
- To be configured in the module
- Number of current inputs
- 4
- Number of Digital inputs/outputs
- 2 Digital inputs
- Power Quality measurements
- THD V1, V2, V3, U12, U23, U31, I1, I2, I3
- Pulse counter
- Yes, 2 Digital inputs
- Reactive Energy accuracy
- Class 2 for the global measurement chain with TE, TR or TF current sensors
- Voltage connection
- Removable spring-cage terminal, 2 x 6 positions, 0.5 … 2.5 mm² solid cable or 0.25 … 1.5 mm² stranded cable with ferrule
- Voltage measurement accuracy
- Class 0.2
- Voltage measurement range Ph/N
- 50-300 VAC
- Voltage measurement range Ph/Ph
- 87-520 VAC
- Voltage measurement type
- AC
- Voltage Sampling rate
- 9.6 kHz
- Voltage transformer
- Optional
- Voltage transformer primary
- To be configured
- Voltage transformer secondary
- To be configured
Safety
- Safety standards
- IEC/EN 61010-1
- UL file number
- E257746
General Product Characteristics
- Device type
- Multifunction Power metering and monitoring device (PMD)
Electrical Characteristics
- Device power consumption (VA)
- ? 2
- Input voltage
- 110-230 VAC +/- 15%
- Power supply connection
- Removable spring-cage terminal, 2 x 2 positions, 0.5 … 2.5 mm² solid cable or 0.25 … 1.5 mm² stranded cable with ferrule
- Power supply frequency
- 50/60 Hz
- Power supply type
- AC