- Net Weight in Kg
- 0.037
- Supplier
- Siemens AG
- Order number
- 6ES7131-6BH00-0BA0
- Address range memory per module maximum [byte]
- 2
- Address range memory per module maximum Note
- =+ 2 bytes for QI information
- Alert function Diagnostics alarm
- Yes
- Color coding of labeling plates for module-specific use usable
- CC00
- Consumed current maximum [mA]
- 90
- Delay time at signal change maximum [µs]
- 20000
- Delay time at signal change minimum [µs]
- 50
- Depth [mm]
- 58
- Design of the sensor connectable 2-wire transmitter
- Yes
- Diagnostics function
- Yes
- Diagnostics function Cable break
- Yes
- Diagnostics function Cable break Note
- Module-wise
- Diagnostics function Diagnostics information readable
- Yes
- Diagnostics function Group fault
- Yes
- Diagnostics function Monitoring of the mains voltage of the electronic
- Yes
- Diagnostics function Short-circuit detection
- No
- Digital input version Type 1 acc. to IEC 61131
- Yes
- Digital input version Type 2 acc. to IEC 61131
- No
- Display version for diagnostic function: Status display expansion modules module diagnostics (traffic light green-red-yellow or DIAG red/green)
- Yes
- Display version for diagnostic function: Status display expansion modules module diagnostics (traffic light green-red-yellow or DIAG red/green) Note
- green/red DIAG LED
- Display version for diagnostic function: Status display transmission channel channel diagnostics LED
- No
- Display version for diagnostic function: Status display transmission channel channel status LED
- Yes
- Display version for diagnostic function: Status display transmission channel channel status LED Note
- Green LED
- Display version for diagnostic function: Supply voltage monitoring Power LED
- Yes
- Display version for diagnostic function: Supply voltage monitoring Power LED Note
- green PWR LED
- Equipment marking acc. to DIN EN 81346-2
- K
- Explosion protection category for dust
- No
- Explosion protection category for gas
- ATEX II 3 G Ex nA II T4 ... T5
- Explosion protection marking for intrinsic safety of related equipment EEx ia
- No
- Explosion protection marking for intrinsic safety of related equipment EEx ib
- No
- Firmware version
- V1.1
- Galvanic isolation at the universal inputs between the channels
- No
- Galvanic isolation at the universal inputs between the channels and backing bus
- Yes
- Galvanic isolation at the universal inputs between the channels and voltage supply of the electronics
- No
- GSD version/revision with PROFIBus required
- GSD Revision 5
- GSD version/revision with PROFINET required
- GSDML V2.3
- Height [mm]
- 73
- Input current at digital input for signal <1> typical [mA]
- 2.5
- Input delay time at the standard inputs for signal <0> to <1> at rated input voltage maximum [µs]
- 20000
- Input delay time at the standard inputs for signal <0> to <1> at rated input voltage minimum [µs]
- 50
- Input delay time at the standard inputs for signal <1> to <0> at rated input voltage maximum [µs]
- 20000
- Input delay time at the standard inputs for signal <1> to <0> at rated input voltage minimum [µs]
- 50
- Input voltage at digital input at DC Rated value [V]
- 24
- Mounting type front mounting
- Yes
- Mounting type rack mounting
- Yes
- Mounting type rail mounting
- Yes
- Mounting type wall mounting
- No
- Number of digital inputs
- 16
- Number of interfaces acc. to PROFINET
- 0
- Number of interfaces acc. to RS 485
- 0
- Operating mode as counter
- No
- Operating mode as digital input
- Yes
- Operating mode oversampling
- No
- Operating voltage as input voltage maximum permissible [V]
- 30
- Operating voltage as input voltage minimum permissible [V]
- -30
- Power loss [W] typical [mW]
- 1700
- Product brandname
- Simatic DP
- Product category
- Digital module input
- Product extension required separate bus coupler for fieldbus connection
- Yes
- Product family
- ET 200SP
- Product feature of the firmware version can be updated
- Yes
- Product function at alarm inputs at rated input voltage parameterizable input delay time
- No
- Product function at the inputs for counters or technological functions at rated input voltage parameterizable input delay time
- No
- Product function at the standard inputs at rated input voltage parameterizable input delay time
- Yes
- Product function at the standard inputs at rated input voltage parameterizable input delay time Note
- 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length)
- Product function for diagnostic function: Encoder supply monitoring parameterizable
- No
- Product function for diagnostic function: Supply voltage monitoring parameterizable
- Yes
- Product function for encoder supply Short-circuit protection
- No
- Product function I&M data
- Yes
- Product function I&M data Note
- I&M0 to I&M3
- Product function MSI
- No
- Product function pulse stretching
- No
- Product function Reverse polarity protection
- Yes
- Product function with 24 V encoder supply Short-circuit protection
- No
- Product type designation
- ET 200SP, DI 16x 24 V DC ST, PU 1
- Product type designation of the racks usable
- BU type A0
- Protection class IP
- IP20
- Protocol is supported PROFIBus protocol
- No
- Protocol is supported PROFINET IO protocol
- No
- Protocol is supported PROFIsafe protocol
- No
- Quiescent current of the 2-wire transducer maximum permissible [mA]
- 1.5
- Software version for PCS 7 application required
- V8.1 SP1
- Software version with STEP 7 required
- V5.5 / -
- Software version with STEP 7 in the TIA Portal required
- V13 SP1
- Suitability for use safety-related function
- No
- Supply voltage at DC Rated value [V]
- 24
- Supply voltage at DC rated value maximum [V]
- 28.8
- Supply voltage at DC rated value minimum [V]
- 19.2
- Supply voltage for encoder supply 24 V
- No
- Type of electrical connection
- Push-in terminal
- Type of isolation test
- 707 V DC (type test)
- Type of voltage at digital input
- DC
- Type of voltage of the supply voltage
- DC
- Value range of the input voltage at digital input for signal <0> detection
- -30 to +5V
- Value range of the input voltage at digital input for signal <1> detection
- =+11 to +30V
- Width [mm]
- 15
- Wire length at digital input shielded maximum [m]
- 1000
- Wire length at digital input unshielded maximum [mm]
- 600000