Additional Information Part Number TPRST065 UNSPSC 39121521 Tariff Code 8536504000 Environment Ambient Air Temperature For Operation -10-50°C without derating || 50-60°C with current derating Shock Resistance 15 gn 11 ms) IEC 60068-2-27 Vibration Resistance 1.5 mm peak to peak 3-13 Hz) IEC 60068-2-6 || 1 gn 13-200 Hz) IEC 60068-2-6 Electromagnetic Compatibility electrostatic discharge immunity test, level 3, 8 kV...

Additional Information

Part Number
TPRST065
UNSPSC
39121521
Tariff Code
8536504000

Environment

Ambient Air Temperature For Operation
-10-50°C without derating || 50-60°C with current derating
Shock Resistance
15 gn 11 ms) IEC 60068-2-27
Vibration Resistance
1.5 mm peak to peak 3-13 Hz) IEC 60068-2-6 || 1 gn 13-200 Hz) IEC 60068-2-6
Electromagnetic Compatibility
electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transient immunity test, level 4, 4 kV, conforming to EN/IEC 61000-4-4 || surge immunity test (differential mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5 || surge immunity test (common mode), level 4, 4 kV, conforming to EN/IEC 61000-4-5 || conducted RF disturbance immunity test, 20 V, conforming to EN/IEC 61000-4-6
Pollution Degree
2
Ambient Air Temperature For Storage
-25-70°C
Protective Treatment
TC
Relative Humidity
5-95 %
Ip Degree Of Protection
IP20
Operating Altitude
0...6561.68 ft (0...2000 m) without derating
Fire Resistance
960°C UL 94 || 850°C IEC 60695-2-1 || 650°C IEC 60695-2-12

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1904009EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1904009EN
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts product

Complementary

Mounting Mode
horizontal and vertical 35 mm symmetrical DIN rail)
Height
167 mm
Product Certifications
CSA || UL || EAC || CCC
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Standards
EN/IEC 60947-1 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Connections - Terminals
EverLink BTR screw connectors 1 1-35 mm² AWG 16...AWG 2)rigid || EverLink BTR screw connectors 2 1-25 mm² AWG 16...AWG 4)rigid || EverLink BTR screw connectors 1 1-35 mm² AWG 16...AWG 2)flexible without cable end || EverLink BTR screw connectors 2 1-25 mm² AWG 16...AWG 4)flexible without cable end || EverLink BTR screw connectors 1 1-35 mm² AWG 16...AWG 2)flexible with cable end || EverLink BTR screw connectors 2 1-25 mm² AWG 16...AWG 4)flexible with cable end
Net Weight
1.248 kg
Metering Type
time device ON || time device switch ON || number of faults || number of switching cycles || number of device power cycles || average current Iavg || average voltage Vavg || max current Imax || max voltage Vmax || active and reactive power with voltage module || active and reactive energy with voltage module || true power factor with voltage module
Maximum Operating Rate
3600 cyc/mn AC-3
Local Signalling
for DS (device status) 1 LED (green/red) || for LS (load status) 1 LED (green/red)
Electrical Durability
1.4 Mcycles 65 A AC-3 440 V || 0.5 Mcycles 80 A AC-1 440 V
Mechanical Durability
6 Mcycles
Operating Time
< 80 ms closing || < 80 ms opening
Width
55 mm
Depth
125 mm
Tightening Torque
5-5 N.m 1-25 mm² hexagonal 4 mm || 8-8 N.m 25-35 mm² hexagonal 4 mm
Protection Type
thermal overload protection || motor overheat || overcurrent || undercurrent || jam || long start || stall || rapid cycle lockout || phase sequence || rapid restart lockout || phase reversal || phase loss || phase unbalance || ground current

Specifications

Current Consumption
80 mA contactor sealed || 500 mA contactor closing
Power Dissipation In W
20.8 W at Ie AC-3
Power Dissipation Per Pole
6.3 W AC-3 - Ith 65 A || 9.6 W AC-1 - Ith 80 A
Average Impedance
1.5 mOhm - Ith 80 A 50 Hz
Reset
remotely or automatically
[Ith] Conventional Free Air Thermal Current
80 A (at 50°C)
[Uc] Control Circuit Voltage
24 V DC supplied by the bus coupler
Rated Breaking Capacity
1000 A at 440 V conforming to IEC 60947
Product Or Component Type
motor starter
Irms Rated Making Capacity
1000 A at 440 V conforming to IEC 60947
Product Name
TeSys island
Thermal Overload Class
class 5¦30
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947-1
Range
TeSys
Device Presentation
direct starter connected to an automation controller through a bus coupler || operational only when connected to a bus coupler
Motor Starter Type
direct on line
Utilisation Category
AC-1 || AC-2 || AC-3 || AC-4
Function Available
upstream voltage presence detection || electrical line and load protection || power and energy monitoring when connected with TPRVM voltage module
[Ie] Rated Operational Current
65 A (at <50°C) at <= 440 V AC-3 || 80 A (at <50°C) at <= 440 V AC-1
Overvoltage Category
III
Thermal Protection Adjustment Range
3.35-65 A
Product Compatibility
TPRBC bus coupler || TPRVM voltage interface module
[Ue] Rated Operational Voltage
<= 690 V AC 47...63 Hz
Maximum Horse Power Rating
5 hp at 120 V AC 60 Hz for 1 phase motors || 10 hp at 240 V AC 60 Hz for 1 phase motors || 20 hp at 208 V AC 60 Hz for 3 phase motors || 20 hp at 240 V AC 60 Hz for 3 phase motors || 40 hp at 480 V AC 60 Hz for 3 phase motors || 50 hp at 600 V AC 60 Hz for 3 phase motors
Motor Power Kw
18.5 kW at 230 V 50 Hz (AC-3) || 30 kW at 380...415 V 50 Hz (AC-3) || 30 kW at 440 V 50 Hz (AC-3) || 37 kW at 500 V 50 Hz (AC-3) || 37 kW at 690 V 50 Hz (AC-3)
[Ui] Rated Insulation Voltage
690 V IEC 60947-4-1 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
Device Short Name
TPRST
Poles Description
3P 3 NO
[Icw] Rated Short-Time Withstand Current
900 A 40°C - 1 s || 520 A 40°C - 10 s || 260 A 40°C - 1 min || 110 A 40°C - 10 min

Returns Policy

You may return most new, unopened items within 30 days of delivery for a full refund. We'll also pay the return shipping costs if the return is a result of our error (you received an incorrect or defective item, etc.).

You should expect to receive your refund within four weeks of giving your package to the return shipper, however, in many cases you will receive a refund more quickly. This time period includes the transit time for us to receive your return from the shipper (5 to 10 business days), the time it takes us to process your return once we receive it (3 to 5 business days), and the time it takes your bank to process our refund request (5 to 10 business days).

If you need to return an item, simply login to your account, view the order using the "Complete Orders" link under the My Account menu and click the Return Item(s) button. We'll notify you via e-mail of your refund once we've received and processed the returned item.

Shipping

We can ship to virtually any address in the world. Note that there are restrictions on some products, and some products cannot be shipped to international destinations.

When you place an order, we will estimate shipping and delivery dates for you based on the availability of your items and the shipping options you choose. Depending on the shipping provider you choose, shipping date estimates may appear on the shipping quotes page.

Please also note that the shipping rates for many items we sell are weight-based. The weight of any such item can be found on its detail page. To reflect the policies of the shipping companies we use, all weights will be rounded up to the next full pound.

Recently Viewed Products