Additional Information
- Part Number
- RM35JA31MW
- UNSPSC
- 39122331
- Tariff Code
- 8536490075
- Country of Origin
- ID
Environment
- Product Certifications
- GL || CSA || GOST || UL || C-tick
- Standards
- IEC 60255-6
- Immunity To Microbreaks
- 50 ms
- Non-Dissipating Shock Wave
- 4 kV IEC 60255-5 || 4 kV IEC 60664-1 || 4 kV IEC 61000-4-5
- Dielectric Test Voltage
- 2 kV AC 50 Hz, 1 min IEC 60255-5 || 2 kV AC 50 Hz, 1 min IEC 60664-1
- Electromagnetic Compatibility
- emission standard for industrial environments conforming to IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 || immunity for industrial environments conforming to NF EN/IEC 61000-6-2
- Shock Resistance
- 15 gn 11 ms IEC 60255-21-1
- Ambient Air Temperature For Operation
- -20-50°C
- Vibration Resistance
- 0.35 mm 5-57.6 Hz)IEC 60068-2-6 || 1 gn 57.6-150 Hz)IEC 60255-21-1
- Ip Degree Of Protection
- IP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
- Pollution Degree
- 3 IEC 60664-1
- Ambient Air Temperature For Storage
- -40-70°C
- Relative Humidity
- 95-95 % 55-55°C IEC 60068-2-30
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1504008EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI1504008EN
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Complementary
- [Us] Rated Supply Voltage
- 24...240 V AC/DC 50/60 Hz +/- 10 %
- Polarity
- no DC
- Safety Reliability Data
- MTTFd = 296.8 years || B10d = 270000
- Maximum Measuring Cycle
- 30 ms measurement cycle as true rms value
- Control Circuit Voltage Limits
- 15 % + 10 % Un
- Hysteresis
- 5-50 % threshold setting
- Insulation Resistance
- >; 500 MOhm 500 V DC between supply and relay output IEC 60255-5 || >; 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 || >; 1 MOhm 500 V DC between supply and measurement IEC 60255-5 || >; 500 MOhm 500 V DC between supply and relay output IEC 60664-1 || >; 500 MOhm 500 V DC between measurement and relay output IEC 60255-5 || >; 1 MOhm 500 V DC between supply and measurement IEC 60664-1
- Measurement Error
- 0.05 %/°C with temperature variation || 1 by volt over the whole range with voltage variation
- Operating Rate
- <= 360 operations/hour full load
- Output Contacts
- 2 C/O
- Contacts Material
- cadmium free
- Marking
- CE : EMC 89/336/EEC || CE : 73/23/EEC
- Operating Position
- any position without derating
- Net Weight
- 0.13 kg
- Threshold Setting
- 10...100 %
- Maximum Switching Voltage
- 250 V AC
- Reset Time
- 1500 ms time delay
- Connections - Terminals
- screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
- [Ui] Rated Insulation Voltage
- 250 V IEC 60664-1
- Overvoltage Category
- III IEC 60664-1
- Supply Voltage Limits
- 20.4-264 V AC/DC
- Mounting Support
- 35 mm symmetrical DIN rail conforming to IEC 60715
- Nominal Output Current
- 5 A
- Local Signalling
- for power ON LED (green) || for relay ON LED (yellow)
- Mechanical Durability
- 30000000 cycles
- Housing Material
- self-extinguishing plastic
- Resistance Across Terminals
- 1 Ohm E2-M terminals || 5 Ohm E1-M terminals || 0.2 Ohm E3-M terminals
- Control Circuit Frequency
- 40...70 Hz +/- 10 %
- Measurement Accuracy
- +/- 10 % of the full scale value
- Width
- 35 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Maximum Power Consumption In W
- 0.6 W DC
- Electrical Durability
- 100000 cycles
- Run-Up Delay At Power-Up
- 0.3 s
- Repeat Accuracy
- +/- 0.5 % input and measurement circuit || +/- 2 % time delay
Specifications
- Minimum Switching Current
- 10 mA 5 V DC
- Maximum Switching Current
- 5 A AC
- Range Of Product
- Harmony Control Relays
- Measurement Range
- 10...100 mA E2-M terminals || 2...20 mA E1-M terminals || 2...500 mA current || 50...500 mA E3-M terminals
- Switching Capacity In Va
- 1250 VA
- Product Or Component Type
- current control relay
- Utilisation Category
- AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || DC-14 IEC 60947-5-1
- Relay Name
- RM35JA
- Contacts Type And Composition
- 2 C/O
- Relay Type
- current control relay
- Time Delay Type
- adjustable 1...20 s, 0 + 10 % on energisation Ti || adjustable 0.3...30 s, 0 + 10 % on crossing the threshold Tt
- Relay Monitored Parameters
- overcurrent or undercurrent in window mode || overcurrent or undercurrent detection
- Maximum Power Consumption In Va
- 3.5 VA AC