Additional Information
- Part Number
- LC3D80P7A64
- UNSPSC
- 39121529
- Tariff Code
- 8536490065
- Country of Origin
- FR
Environment
- Mechanical Robustness
- vibrations contactor open2 Gn, 5...300 Hz || shocks contactor open8 Gn for 11 ms || vibrations contactor closed3 Gn, 5...300 Hz || shocks contactor closed10 Gn for 11 ms
- Ambient Air Temperature For Operation
- -40-60°C || 60-70°C with derating
- Pollution Degree
- 3
- Insulation Resistance
- > 10 MOhm for signalling circuit
- Flame Retardance
- V1 conforming to UL 94
- Ambient Air Temperature For Storage
- -60-80°C
- Protective Treatment
- TH IEC 60068-2-30
- Ip Degree Of Protection
- IP20 front face IEC 60529
- Operating Altitude
- 9842.52 ft (3000 m)
- Fire Resistance
- 850°C IEC 60695-2-1
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP110205EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Circularity Profile
- N/A
- Eu Rohs Directive
- Compliant
Complementary
- Non-Overlap Time
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Minimum Switching Current
- 5 mA for signalling circuit
- Height
- 143 mm
- Control Circuit Voltage Limits
- drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55°C) || operational: 0.8...1.1 Uc at 50 Hz (at <55°C) || operational: 0.85...1.1 Uc at 60 Hz (at <55°C)
- Starting Time
- 30 s
- Net Weight
- 5.4 kg
- Inrush Power In Va
- 140-140 VA 60 Hz cos phi 0.75 (at 20°C) || 160-160 VA 50 Hz cos phi 0.75 (at 20°C)
- Connections - Terminals
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminals 1 4-50 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 4-25 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 4-50 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 2 4-16 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 1 4-50 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminals 2 4-25 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end
- Coil Technology
- without built-in suppressor module
- Maximum Operating Rate
- 30 cyc/h 60°C
- Signalling Circuit Frequency
- 25...400 Hz
- Tightening Torque
- control circuit 1.2 N.m screw clamp terminals flat ˜ 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m screw clamp terminals flat ˜ 6...8 mm
- Mechanical Durability
- 4 Mcycles
- Auxiliary Contacts Type
- mechanically linked IEC 60947-5-1 3 x 1 NO + 1 NC || mirror contact IEC 60947-4-1 3 x 1 NC
- Hold-In Power Consumption In Va
- 13-13 VA 60 Hz cos phi 0.3 (at 20°C) || 15-15 VA 50 Hz cos phi 0.3 (at 20°C)
- Switching Voltage
- 17 V signalling circuit
- Width
- 311 mm
- Depth
- 183 mm
- Heat Dissipation
- 4-5 W 50/60 Hz
Specifications
- Product Certifications
- RINA || GL || UL || LROS (Lloyds register of shipping) || DNV || CCC || GOST || BV || CSA
- Interlocking Type
- mechanical
- [Uc] Control Circuit Voltage
- 230 V AC 50/60 Hz
- [Ue] Rated Operational Voltage
- power circuit <= 690 V AC 25...400 Hz
- Standards
- EN 60947-4-1 || IEC 60947-4-1 || EN 60947-5-1 || UL 508 || IEC 60947-5-1 || CSA C22.2 No 14
- Pole Contact Composition
- 3 x 3 NO
- Mounting Support
- plate
- Control Circuit Type
- AC 50/60 Hz
- Contactor Application
- motor control
- Product Or Component Type
- star delta starter
- Product Name
- TeSys Deca
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947
- Range
- TeSys
- Device Presentation
- pre-wired
- Utilisation Category
- AC-3
- [Ie] Rated Operational Current
- 80 A (at <60°C) at <= 440 V AC AC-3 for power circuit
- Auxiliary Contact Composition
- 1 NC KM2 line contactor || 1 NO KM3 delta contactor
- Electrical Durability
- 10 Mcycles 80 A AC-3 <= 440 V
- Overvoltage Category
- III
- Motor Power Kw
- 37 kW 220/230 V AC 50/60 Hz || 75 kW 380/400 V AC 50/60 Hz || 75 kW 415 V AC 50/60 Hz || 75 kW 440 V AC 50/60 Hz
- [Ui] Rated Insulation Voltage
- power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || signalling circuit 1000 V IEC 60947-1
- Device Short Name
- LC3D
- Poles Description
- 3 x 3P