Additional Information
- Part Number
- LC2F150
- UNSPSC
- 39121529
- Tariff Code
- 8536490065
- Country of Origin
- CZ
Specifications
- Product Certifications
- CB || RMRoS || DNV || ABS || UL || CCC || CSA || LROS (Lloyds register of shipping) || RINA || UKCA
- Interlocking Type
- mechanical
- [Ue] Rated Operational Voltage
- <= 1000 V AC 50/60 Hz || <= 460 V DC
- Power Dissipation Per Pole
- 8 W AC-3
- Average Impedance
- 0.35 mOhm - Ith 250 A 50 Hz
- Auxiliary Contact Composition
- 1 NO
- [Ith] Conventional Free Air Thermal Current
- 250 A 40°C
- Standards
- EN 60947-4-1 || JIS C8201-4-1 || EN 60947-1 || IEC 60947-4-1 || IEC 60947-1
- Mounting Support
- plate
- Contactor Application
- resistive load || motor control
- Rated Breaking Capacity
- 1200 A IEC 60947-4-1
- Product Or Component Type
- reversing contactor
- Irms Rated Making Capacity
- 1500 A AC IEC 60947-4-1
- Product Name
- TeSys F
- Associated Fuse Rating
- 160 A aM <= 440 V || 250 A gG <= 440 V
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Connections - Terminals
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit connector 1 120-120 mm² || power circuit lugs-ring terminals 1 120-120 mm² || power circuit bar 2 25 x 3 mm
- Range
- TeSys
- Pole Contact Composition
- 3 NO
- Device Presentation
- preassembled with reversing power busbar
- Utilisation Category
- AC-3 || AC-1
- [Ie] Rated Operational Current
- 250 A 40°C) <= 440 V AC AC-1 || 150 A 55°C) <= 440 V AC AC-3
- Tightening Torque
- control circuit 1.2 N.m || power circuit 18 N.m
- Poles Description
- 3P
- Overvoltage Category
- III
- Motor Power Kw
- 65 kW 1000 V AC 50/60 Hz || 75 kW 380...400 V AC 50/60 Hz || 80 kW 415 V AC 50/60 Hz || 80 kW 440 V AC 50/60 Hz || 90 kW 500 V AC 50/60 Hz || 40 kW 220...240 V AC 50/60 Hz || 100 kW 660...690 V AC 50/60 Hz
- [Ui] Rated Insulation Voltage
- 1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
- Device Short Name
- LC2F
- [Icw] Rated Short-Time Withstand Current
- 1200 A 40°C - 10 s || 700 A 40°C - 30 s || 600 A 40°C - 1 min || 450 A 40°C - 3 min || 350 A 40°C - 10 min
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP111201EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI111214EN_V1
- Eu Rohs Directive
- Compliant
Environment
- Mechanical Robustness
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed6 Gn, 5...300 Hz || shocks contactor open9 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Ambient Air Temperature For Operation
- -5-55°C
- Height
- 170 mm
- Net Weight
- 7.56 kg
- Ambient Air Temperature For Storage
- -60-80°C
- Protective Treatment
- TH
- Ip Degree Of Protection
- IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
- Operating Altitude
- 9842.52 ft (3000 m) without derating
- Fire Resistance
- 850°C IEC 60695-2-1
- Width
- 345 mm
- Depth
- 171 mm
- Permissible Ambient Air Temperature Around The Device
- -40-70°C