Additional Information
- Part Number
- ABLP1A24062
- UNSPSC
- 39121004
- Tariff Code
- 8504409520
- Country of Origin
- CN
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2007017EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI2007017EN
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Specifications
- Range Of Product
- Modicon Power Supply
- Output Voltage
- 24 V DC
- Product Or Component Type
- power supply
- Power Supply Type
- regulated switch mode
- Input Voltage
- 100...120 V AC single phase || 200...240 V AC single phase
- Power Supply Output Current
- 6.25 A
- Kw Rating
- 150 W
- Enclosure Material
- Aluminum
Environment
- Standards
- IEC 62368-1 || EN/IEC 61010-1 || EN 61010-2-201 || EN/IEC 61204-3 || IEC 61000-6-1 || IEC 61000-6-2 || IEC 61000-6-3 || IEC 61000-6-4 || IEC 61000-3-2 || EN 61000-3-3 || UL 62368-1 || UL 61010-1 || UL 61010-2-201 || CSA C22.2 No 62368-1 || CSA C22.2 No 61010-1 || CSA C22.2 No 61010-2-201 || IEC 60335-1 || EN/IEC 62368-1
- Ambient Air Temperature For Operation
- -30--25°C with current derating of 4 % per°C mounting position B, G < 6561.68 ft (2000 m) || -25-50°C without derating mounting position B, G < 6561.68 ft (2000 m) || 50-70°C with current derating of 2 % per°C mounting position B, G < 6561.68 ft (2000 m)
- Product Certifications
- CE || cULus || EAC || RCM || CB Scheme || KC
- Pollution Degree
- 2
- Electromagnetic Compatibility
- immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2 || immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2 || immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3 || immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3 || immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3 || immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4 || surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5 || surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5 || immunity to conducted RF disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6 || immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8 || immunity to voltage dips conforming to IEC 61000-4-11 || disturbing field emission conforming to EN 55016-2-3 || limits for harmonic current emissions conforming to IEC 61000-3-2 || conforming to EN 55016-1-2 || conforming to EN 55016-2-1
- Shock Resistance
- 150 m/s² 11 ms
- Vibration Resistance
- 3 mm 2-9 Hz)IEC 60068-2-6 || 10 m/s² 9-200 Hz)IEC 60068-2-6
- Ip Degree Of Protection
- IP10
- Operating Altitude
- 5000 m
- Electrical Shock Protection Class
- class I
- Electromagnetic Emission
- conducted emissions IEC 61000-6-3 || radiated emissions IEC 61000-6-4
Complementary
- Output Coupling
- parallel || serial
- Height
- 30 mm
- Residual Ripple
- < 170 mV
- Status Led
- 1 LED (Green) output voltage
- Holding Time
- > 20 ms 115 V AC || > 40 ms 230 V AC
- Efficiency At Full Load
- 90...132 V AC || 170...264 V AC
- Earthing System
- TN || TT || IT
- Connections - Terminals
- screw connection 0.75...2.5 mm², AWG 18...AWG 14) without wire end ferrule || screw connection 0.75...1.5 mm², AWG 18...AWG 16) with wire end ferrule
- Dielectric Strength
- 3750 V AC with input to output
- Network Frequency Limits
- 50-60 Hz
- Current Consumption
- < 3.2 A 115 V AC || < 1.9 A 230 V AC
- Supply
- SELV IEC 60950-1 || SELV IEC 60204-1 || SELV IEC 60364-4-41
- Net Weight
- 0.36 kg
- Maximum Leakage Current
- 1 mA 240 V AC
- Input Protection Type
- integrated fuse (not interchangeable) 4 A
- Output Protection Type
- against overload and short-circuits automatic reset || against over temperature manual reset || against overvoltage manual reset
- Service Life
- 10 year(s)
- Meantime Between Failure [Mtbf]
- 700000 h at 25°C, full load conforming to SR 332
- Power Dissipation In W
- 29 W
- Output Voltage Limits
- 21.6...26.4 V
- Mounting Support
- top hat type TH35-15 rail IEC 60715 || top hat type TH35-7.5 rail IEC 60715 || double-profile DIN rail || panel mounting
- Load Capacitance
- 7000 µF
- Response Time
- < 500 ms
- Line And Load Regulation
- < 0.5 % network 0 to 100 % load at 25°C || < 1 % network full voltage range in line at 25°C
- Width
- 97 mm
- Overvoltage Category
- II
- Inrush Current
- 35 A 115 V || 70 A 230 V
- Efficiency
- 88.8 % 230 V AC
- Depth
- 159 mm
- Power Factor
- 0.55 at 115 V AC || 0.45 at 230 V AC