Additional Information
- Part Number
- 101126705
- ETIM
- Group Code : EG000019
- Group Description : Relays
- Class Description : Device for monitoring of safety-related circuits
- Class Code : EC001449
- Version : 7
Electrical data - Relay outputs (auxiliary contacts)
- Switching capacity, maximum
- 24 VDC
- Switching capacity, maximum
- 2 A
Electrical data
- Frequency range
- 50 Hz | 60 Hz
- Operating voltage
- 230 VAC -15 % / +15 %
- Rated operating voltage
- 230 VAC
- Rated AC voltage for controls, 50 Hz, minimum
- 20.4 VAC
- Rated control voltage at AC 50 Hz, maximum
- 26.4 VAC
- Rated AC voltage for controls, 60 Hz, minimum
- 20.4 VAC
- Rated control voltage at AC 60 Hz, maximum
- 26.4 VAC
- Electrical power consumption
- 5 W
- Contact resistance, maximum
- 0.1 ?
- Note (Contact resistance)
- in new state
- Drop-out delay in case of power failure, typically
- 80 ms
- Drop-out delay in case of emergency, typically
- 20 ms
- Pull-in delay at automatic start, maximum, typically
- 100 ms
- Pull-in delay at RESET, typically
- 20 ms
Note
- Note (General)
- Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.
Mechanical data - Dimensions
- Width
- 55 mm
- Height
- 75 mm
- Depth
- 110 mm
Ambient conditions - Insulation values
- Rated impulse withstand voltage U
- 4 kV
- Overvoltage category
- III
- Degree of pollution
- 2
Electrical data - Digital Output
- Voltage, Utilisation category DC-12
- 24 VDC
- Current, Utilisation category DC-12
- 0.1 A
General data - Features
- Wire breakage detection
- Yes
- Cross-circuit detection
- Yes
- Automatic reset function
- Yes
- Reset after disconnection of supply voltage
- Yes
- Earth connection detection
- Yes
- Integral system diagnostics, status
- Yes
- Number of LEDs
- 1
- Number of normally closed (NC)
- 1
- Number of normally open (NO)
- 1
- Number of undelayed semi-conductor outputs with signaling function
- 2
- Number of safety contacts
- 3
- Number of signalling outputs
- 2
General data
- Standards
- BG-GS-ET-20 | EN IEC 62061 | EN ISO 13849-1 | EN IEC 60947-5-1 | EN IEC 60947-5-3 | EN IEC 60947-5-5 | EN IEC 60204-1 | EN IEC 60947-1
- Enclosure material
- Glass-fibre, reinforced thermoplastic
- Gross weight
- 450 g
Safety classification
- Standards
- EN IEC 61508
- Performance Level, up to
- d
- Category
- 3
- PFH value
- 1.00 x 10?? /h
- Safety Integrity Level (SIL), suitable for applications in
- 2
- Mission time
- 20 Year(s)
Wiring example
- Note (Wiring diagram)
- The wiring diagram is shown with guard doors closed and in de-energised condition. | The ISD tables (Intergral System Diagnostics) for analysis of the fault indications and their causes are shown in the appendix. | To monitor one guard door at plants with dangerous run-on movements up to PL d and Category 3 | Monitoring time for unlocking of solenoid interlocks | The solenoid interlock releases the guard device only when the set time has elapsed. The time begins to run when the power contactors have dropped out.
Other data
- Note (applications)
- Fail-safe delay timer
Ambient conditions
- Degree of protection of the enclosure
- IP40
- Degree of protection of the mounting space
- IP54
- Degree of protection of clips or terminals
- IP20
- Ambient temperature
- +0 ... +55 °C
- Storage and transport temperature, minimum
- -25 °C
- Storage and transport temperature, maximum
- +70 °C
- Resistance to vibrations
- 10 ... 55 Hz, Amplitude 0.35 mm
- Restistance to shock
- 30 g / 11 ms
Mechanical data - Connection technique
- Termination
- rigid or flexible | Screw terminals M20 x 1.5
- Cable section, maximum
- 4 mm²
- Note (Cable section)
- All indications including the conductor ferrules.
- Tightening torque of Clips
- 0.4 Nm
Electrical data - Safe relay outputs
- Voltage, Utilisation category AC-15
- 250 VAC
- Current, Utilisation category AC-15
- 2 A
- Voltage, Utilisation category DC-13
- 24 VDC
- Current, Utilisation category DC-13
- 2 A
- Switching capacity, minimum
- 10 VDC
- Switching capacity, minimum
- 10 mA
- Switching capacity, maximum
- 250 VAC
- Switching capacity, maximum
- 8 A
Mechanical data
- Mounting
- Snaps onto standard DIN rail to EN 60715
Specifications
- Width
- 55 mm
- Height
- 75 mm
- Depth
- 110 mm
Approvals - Standards
- Certificates
- cULus
Electrical data - Electromagnetic compatibility (EMC)
- EMC rating
- EMC-Directive
Electrical data - Digital inputs
- Input signal, HIGH Signal "1"
- 10 … 30 VDC
- Input signal, LOW Signal "0"
- 0 … 2 VDC
- Conduction resistance, maximum
- 40 ?
Integral system diagnosis (ISD)
- Note (ISD -Faults)
- The following faults are registered by the safety monitoring modules and indicated by ISD.
- Faults
- Failure of the safety relay to pull-in or drop-out | Fault on the input circuits or the relay control circuits of the safety monitoring module | Difference in time setting between channel I and channel II | Cross conclusions to the input lines | Interruption of the input connections