Additional Information
- Part Number
- 2901425
- UPC
- 4046356592031
- Country of Origin
- DE
- ETIM
- Group Code : EG000019
- Group Description : Relays
- Class Description : Device for monitoring of safety-related circuits
- Class Code : EC001449
- Version : 7
Input data
- Input voltage range
- 110 V AC/DC - 120 V AC/DC
- Input voltage range in reference to UN
- 0.85 - 1.1
- Typical input current at UN
- 38 mA
- Voltage at input/start and feedback circuit
- ~ 24 V DC
- Typical response time
- 40 ms (man. start)
- Typ. starting time with Us
- 330 ms (when controlled via A1)
- Typical release time
- 60 ms (when controlled via A1)
- Typical release time
- 20 ms (when controlled via S11/S12 and S21/S22)
- Concurrence input 1/2
- ˆž
- Recovery time
- 1 s
- Operating voltage display
- Green LED
- Status display
- Green LED
- Protective circuit
- Surge protection Varistor 275 VRMS (A1-A2)
- Protective circuit
- Surge protection Varistor
- Maximum switching frequency
- 0.5 Hz
- Max. permissible overall conductor resistance
- 50 ©
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 22.5 mm
- Height
- 112 mm
- Depth
- 114.5 mm
Connection data
- Connection method
- Push-in connection
- Pluggable
- Yes
- Conductor cross section solid min.
- 0.2 mm²
- Conductor cross section solid max.
- 1.5 mm²
- Conductor cross section flexible min.
- 0.2 mm²
- Conductor cross section flexible max.
- 1.5 mm²
- Conductor cross section AWG min.
- 24
- Conductor cross section AWG max.
- 16
- Stripping length
- 8 mm
Output data
- Contact type
- 3 enabling current paths
- Contact type
- 1 signaling current path
- Contact material
- AgSnO‚‚, + 0.2 µm Au
- Maximum switching voltage
- 250 V AC/DC
- Minimum switching voltage
- 10 V AC/DC
- Limiting continuous current
- 6 A (N/O contact)
- Limiting continuous current
- 5 A (N/C contact)
- Maximum inrush current
- 6 A
- Inrush current, minimum
- 10 mA
- Sq. Total current
- 72 A²
- Interrupting rating (ohmic load) max.
- 144 W (24 V DC, τ = 0 ms)
- Interrupting rating (ohmic load) max.
- 230 W (48 V DC, τ = 0 ms)
- Interrupting rating (ohmic load) max.
- 68 W (110 V DC, τ = 0 ms)
- Interrupting rating (ohmic load) max.
- 88 W (220 V DC, τ = 0 ms)
- Interrupting rating (ohmic load) max.
- 2000 VA (250 V AC, τ = 0 ms)
- Maximum interrupting rating (inductive load)
- 48 W (24 V DC, τ = 40 ms)
- Maximum interrupting rating (inductive load)
- 40 W (48 V DC, τ = 40 ms)
- Maximum interrupting rating (inductive load)
- 35 W (110 V DC, τ = 40 ms)
- Maximum interrupting rating (inductive load)
- 33 W (220 V DC, τ = 40 ms)
- Switching capacity min.
- 100 mW
- Mechanical service life
- approx. 10�· cycles
- Switching capacity (360/h cycles)
- 6 A (24 V DC)
- Switching capacity (360/h cycles)
- 5 A (230 V AC)
- Output fuse
- 10 A gL/gG NEOZED (N/O contact)
- Output fuse
- 6 A gL/gG NEOZED (N/C contact)
Ambient conditions
- Ambient temperature (operation)
- -25°C - 55°C
- Ambient temperature (storage/transport)
- -40°C - 85°C
- Max. permissible relative humidity (operation)
- 75 % (on average, 85% infrequently, non-condensing)
- Max. permissible humidity (storage/transport)
- 75 % (on average, 85% infrequently, non-condensing)
- Maximum altitude
- ‰¤ 2000 m (Above sea level)
Environmental Product Compliance
- REACh SVHC
- Lead 7439-92-1
- China RoHS
- Environmentally Friendly Use Period = 50 years
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
Standards and Regulations
- Designation
- Air clearances and creepage distances between the power circuits
- Standards/regulations
- DIN EN 50178/VDE 0160
- Rated insulation voltage
- 250 V AC
- Rated surge voltage/insulation
- 4 kV / basic insulation (safe isolation, reinforced insulation, and 6 kV between A1-A2/logic/enabling and signaling current paths)
- Degree of pollution
- 2
- Overvoltage category
- III
- Shock
- 15g
- Vibration (operation)
- 10 Hz - 150 Hz, 2g
Safety-related characteristic data
- Stop category
- 0
- Designation
- IEC 61508 - High demand
- Safety Integrity Level (SIL)
- 3
- Designation
- IEC 61508 - Low demand
- Designation
- EN ISO 13849
- Performance level (PL)
- e
- Category
- 4
- Designation
- EN 62061
- Safety Integrity Level Claim Limit (SIL CL)
- 3
- Designation
- EN 50156