Additional Information Part Number 2882307 UPC 4046356073493 ETIM Group Code : EG000021 Group Description : Earthing, lightning and surge protection Class Description : Surge protection device for power supply & information tech. Class Code : EC001473 Version : 7 Connection (protective circuit, power supply) Connection method Grounding plug/socket Connection method IN Protective contact plug CEE7 Connection method OUT Protective contact...

Additional Information

Part Number
2882307
UPC
4046356073493
ETIM
Group Code : EG000021
Group Description : Earthing, lightning and surge protection
Class Description : Surge protection device for power supply & information tech.
Class Code : EC001473
Version : 7

Connection (protective circuit, power supply)

Connection method
Grounding plug/socket
Connection method IN
Protective contact plug CEE7
Connection method OUT
Protective contact socket CEE7

Protective circuit, power supply

EN type
T3
Nominal voltage UN
230 V AC
Arrester rated voltage UC (L-N)
275 V AC
Arrester rated voltage UC (L-PE)
360 V AC
Arrester rated voltage UC (N-PE)
360 V AC
Nominal frequency fN
50 Hz (60 Hz)
Rated load current IL
16 A (30°C)
Standby power consumption PC
¤ 1 VA
Residual current IPE
¤ 5 µA
Nominal discharge current In (8/20) µs
3 kA (> 5x)
Combination wave UOC
4 kV
Energy absorption symmetrical
140 J (L-N)
Enery absorption, asymmetrical
220 J (L(N)-PE)
Voltage protection level Up (L-N)
¤ 1.2 kV
Voltage protection level Up (L-PE)
¤ 1.5 kV
Voltage protection level Up (N-PE)
¤ 1.5 kV
Response time (L-N)
¤ 25 ns
Response time (L-PE)
¤ 100 ns
Response time (N-PE)
¤ 100 ns
Surge protection fault message
optical
Max. required back-up fuse
16 A (gG / B / C)

Ambient conditions

Ambient temperature (operation)
-25°C - 75°C
Ambient temperature (storage/transport)
-25°C - 75°C

Connection, equipotential bonding, information technology

Connection method
Via protective contact plug

Protective circuit, information technology

Arrester rated voltage UC
24 V DC
Rated current
1.5 A (25°C)
Operating effective current IC at UC
¤ 1 µA
Residual current IPE
¤ 1 µA
Insulation resistance Riso
70 M©
Nominal discharge current In (8/20) µs (line-earth)
2.5 kA
Nominal discharge current In (8/20) µs (line-shield)
2.5 kA
Nominal discharge current In (8/20) µs (shield-earth)
5 kA
Voltage protection level Up (line-shield)
¤ 700 V (C2 - 2 kA)
Voltage protection level Up (shield-earth)
¤ 1.2 kV (C2 - 5 kA)
Response time tA (line-shield)
¤ 100 ns
Response time tA (shield-earth)
¤ 100 ns
Input attenuation aE, asym.
typ. 0.3 dB ( ¤ 2.4 GHz)
Cut-off frequency fg (3 dB), asym. (shield) in 75 Ohm system
typ. 2.5 GHz
Frequency range
0 Hz - 2400 MHz
Capacity asymmetrical (shield)
typ. 10 pF
Nominal pulse current ian (10/1000) µs, asym. (shield)
120 A
Residual voltage at In (line-shield)
¤ 40 V
Residual voltage at In (shield-earth)
¤ 50 V
Impulse durability (line-shield)
C2 - 4 kV/2 kA
Impulse durability (line-shield)
C3 - 7.5 kV/100 A
Impulse durability (shield-earth)
C2 - 10 kV/5 kA
Impulse durability (shield-earth)
C3 - 7.5 kV/100 A
Impulse durability (shield-earth)
D1 - 1 kA
Alternating current carrying capacity (line-shield)
5 A - 1 s
Alternating current carrying capacity (shield-earth)
10 A - 1 s
Pulse reset time (line-shield)
¤ 4 s

Standards (protective circuit, information technology)

IEC test classification
C2
IEC test classification
C3
IEC test classification
D1

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1

Power supply, general

Connection method
F connector
Connection method IN
F connector, female
Connection method OUT
F connector, female

Returns Policy

You may return most new, unopened items within 30 days of delivery for a full refund. We'll also pay the return shipping costs if the return is a result of our error (you received an incorrect or defective item, etc.).

You should expect to receive your refund within four weeks of giving your package to the return shipper, however, in many cases you will receive a refund more quickly. This time period includes the transit time for us to receive your return from the shipper (5 to 10 business days), the time it takes us to process your return once we receive it (3 to 5 business days), and the time it takes your bank to process our refund request (5 to 10 business days).

If you need to return an item, simply login to your account, view the order using the "Complete Orders" link under the My Account menu and click the Return Item(s) button. We'll notify you via e-mail of your refund once we've received and processed the returned item.

Shipping

We can ship to virtually any address in the world. Note that there are restrictions on some products, and some products cannot be shipped to international destinations.

When you place an order, we will estimate shipping and delivery dates for you based on the availability of your items and the shipping options you choose. Depending on the shipping provider you choose, shipping date estimates may appear on the shipping quotes page.

Please also note that the shipping rates for many items we sell are weight-based. The weight of any such item can be found on its detail page. To reflect the policies of the shipping companies we use, all weights will be rounded up to the next full pound.

Recently Viewed Products