Additional Information
- Part Number
- 2701491
- UPC
- 4046356762854
- Country of Origin
- DE
- ETIM
- Group Code : EG000024
- Group Description : PLC's
- Class Description : Fieldbus, decentr. periphery - digital I/O module
- Class Code : EC001599
- Version : 7
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 60 mm
- Height
- 185 mm
- Depth
- 38 mm
- Note on dimensions
- The height is 194.5 mm including the mounting plate. With fixing clips pulled out, the height is 212 mm. The depth is 38 mm including the mounting plate (30.5 mm without the mounting plate).
- Drill hole spacing
- 198.5 mm
System limits of the bus coupler
- Designation
- EtherNet/IP„
- Equipment type
- EtherNet/IP„ slave
- System-specific protocols
- EtherNet/IP„ protocols ACD
- System-specific protocols
- EtherNet/IP„ protocols DLR
- System-specific protocols
- EtherNet/IP„ protocols IGMP v2
- Protocols supported
- SNMP v1
- Protocols supported
- HTTP
- Protocols supported
- TFTP
- Protocols supported
- FTP
- Protocols supported
- BootP
- Protocols supported
- DHCP
- Specification
- CIP Edition 3.11 EIP adaptation of CIP 1.12
Supply
- Designation
- Module electronics and sensors (US)
- Connection method
- M12 connector (T-coded)
- Number of positions
- 4
- Supply voltage
- 24 V DC
- Supply voltage range
- 19.5 V DC - 31.2 V DC (including all tolerances, including ripple)
- Current consumption
- typ. 180 mA ±15 % (at 24 V DC)
- Designation
- Actuators (UA)
- Supply voltage range
- 18 V DC - 31.2 V DC (including all tolerances, including ripple)
- Current consumption
- typ. 28 mA ±15 % (at 24 V DC)
Digital inputs
- Input name
- Digital inputs at pin 2 for type A ports
- Description of the input
- IEC 61131-2 type 1
- Number of inputs
- 4
- Protective circuit
- Overload protection, short-circuit protection of sensor supply
- Nominal input voltage UIN
- 24 V DC
- Nominal input current at UIN
- typ. 3 mA
- Input voltage range "0" signal
- -0.3 V DC - 5 V DC
- Input voltage range "1" signal
- 15 V DC - 30 V DC
- Description of the input
- IO-Link ports in digital input (DI) mode
- Connection method
- M12 connector, X01 - X04 have double occupancy
- Connection technology
- 3-wire
- Number of inputs
- max. 8 (EN 61131-2 type 1)
- Nominal input current
- typ. 3 mA
- Sensor current per channel
- max. 200 mA (from L+/L-)
- Total sensor current
- max. 1.6 A (from L+/L-)
- Input filter time
- < 1000 µs
- Input frequency
- 0.5 kHz
- Type of protection
- Overload protection
- Type of protection
- Short-circuit protection for the sensor supply
Ambient conditions
- Ambient temperature (operation)
- -25°C - 60°C
- Ambient temperature (storage/transport)
- -25°C - 85°C
- Permissible humidity (operation)
- 5 % - 95 %
- Permissible humidity (storage/transport)
- 5 % - 95 %
- Air pressure (operation)
- 70 kPa - 106 kPa (up to 3000 m above sea level)
- Air pressure (storage/transport)
- 70 kPa - 106 kPa (up to 3000 m above sea level)
- Degree of protection
- IP65/IP67
Environmental Product Compliance
- China RoHS
- Environmentally Friendly Use Period = 25;
- China RoHS
- For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'
Electrical isolation
- Test section
- 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection (Ethernet 1) 500 V AC 50 Hz 1 min.
- Test section
- 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min.
- Test section
- 24 V supply (communications power and sensor supply, IO-Link ports)/FE 500 V AC 50 Hz 1 min.
- Test section
- Bus connection (Ethernet 1)/FE 500 V AC 50 Hz 1 min.
- Test section
- Bus connection (Ethernet 2)/FE 500 V AC 50 Hz 1 min.
- Test section
- Bus connection (Ethernet 1)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min.
- Test section
- 24 V supply (actuator supply)/24 V supply (communications power and sensor supply, IO-Link ports) 500 V AC 50 Hz 1 min.
- Test section
- 24 V supply (actuator supply)/bus connection (Ethernet 1) 500 V AC 50 Hz 1 min.
- Test section
- 24 V supply (actuator supply)/bus connection (Ethernet 2) 500 V AC 50 Hz 1 min.
- Test section
- 24 V supply (actuator supply)/FE 500 V AC 50 Hz 1 min.
Digital outputs
- Output description
- IO-Link ports in digital output (DO) mode
- Connection method
- M12 connector, X01 - X04 have double occupancy
- Connection technology
- 3-wire
- Number of outputs
- max. 8
- Nominal output voltage
- 24 V DC
- Maximum output current per channel
- 150 mA
- Maximum output current per device
- 1.2 A
- Nominal load, ohmic
- 3.6 W (160 Ω, at nominal load)
- Nominal load, inductive
- 3.6 VA (0.8 H, 160 Ω, at nominal load)
- Signal delay
- max. 150 µs (when switched on)
- Signal delay
- max. 200 µs (when switched off)
- Switching rate
- 1 per second, maximum (at nominal inductive load)
- Limitation of the voltage induced on circuit interruption
- -15 V DC
- Output voltage when switched off
- max. 1 V
- Output current when switched off
- max. 300 µA
- Type of protection
- Overload protection
- Type of protection
- Short-circuit protection
- Behavior with overload
- Shutdown with automatic restart
Interfaces
- Designation
- EtherNet/IP„
- No. of channels
- 2
- Connection method
- M12 fast connection technology
- Note on the connection method
- D-coded
- Designation connection point
- Copper cable
- Transmission speed
- 10/100 Mbps (with auto negotiation)
- Number of positions
- 4
Standards and Regulations
- Mechanical tests
- Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
- Mechanical tests
- Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse
- Mechanical tests
- Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
- Protection class
- III (IEC 61140, EN 61140, VDE 0140-1)