OMRON H3DK-M2 AC/DC24-240-Dropship Automation

OMRON H3DK-M2 AC/DC24-240

SKU: DA-267745
Availability: 1 In Stock
Product Type: simple
Additional Information Part Number H3DK-M2 AC/DC24-240 Ratings / Performance Rated supply voltage 24 to 240VAC 50/60 Hz Rated supply voltage 24 to 240VDC ripple: 20% max. Operating voltage range 85% to 110% of rated supply voltage Input signals Start Input method Voltage input Voltage input High (logic) level: 20.4 to 264 VAC/DC Voltage input Low (logic) level: 0 to 2.4...

Additional Information

Part Number
H3DK-M2 AC/DC24-240

Ratings / Performance

Rated supply voltage
24 to 240VAC 50/60 Hz
Rated supply voltage
24 to 240VDC ripple: 20% max.
Operating voltage range
85% to 110% of rated supply voltage
Input signals
Start
Input method
Voltage input
Voltage input
High (logic) level: 20.4 to 264 VAC/DC
Voltage input
Low (logic) level: 0 to 2.4 VAC/DC
Minimum input signal width
50 ms min. (Start input)
Power consumption ( Relay ON )
6.6VA(at 240 VAC)
Power consumption ( Relay ON )
1.2W(at 24 VDC)
Power consumption ( Relay OFF )
(at 240 VAC)
Power consumption ( Relay OFF )
(at 24 VDC)
Reset voltage
10% max. of rated supply voltage
Number of time ranges
8
Time ranges
0.1s~1.2s / 1s~12s / 10s~120s / 1min~12min / 10min~120min / 1h~12h / 10h~120h / 100h~1200h
Operating mode
ON delay, Flicker OFF start, Flicker ON start, Signal ON/OFF delay, Signal OFF delay, Interval, Signal ON/OFF delay, One shot output
Control output (Type)
Relay output (DPDT)
Control output (Contact output)
Switching capacities (resistive load (cos (phi) = 1)): 250VAC 5A / 30VDC 5A
Control output (Contact output)
Switching capacities (resistive load (cos (phi) = 1)): 250VAC 5A / 125VDC 0.15A
Control output (Contact output)
Switching capacities (resistive load (cos (phi) = 1)): 250VAC 5A / 125VDC 0.1A
Control output (Contact output)
Minimum applicable load: 10 mA at 5 VDC (failure level: P)
Ambient temperature
Operating: -20 to 55°C
Ambient temperature
Storage: -40 to 70°C
Ambient humidity
Operating: 25~85%
Accuracy of operating time
+/- 1% max.(FS)
Accuracy of operating time
(+/- 1% +/- 10 ms max. in a range of 1.2 s)
Setting error
-10 to 10% +/- 0.05 s max. (FS)
Influence of voltage
+/- 0.5% FS max. (+/- 0.5% +/- 10 ms max. in a range of 1.2 s)
Influence of temperature
+/- 2% FS max. (+/- 2% +/- 10 ms max. in a range of 1.2 s)
Insulation resistance
100 MΩ (at 500 VDC)
Dielectric strength
between current carrying metal parts and non-current carrying metal parts: 2000 VAC, 50/60 Hz for 1 min
Dielectric strength
between control output terminals and operating circuit: 2000 VAC, 50/60 Hz for 1 min
Dielectric strength
between non-continuous contacts: 1000 VAC, 50/60 Hz for 1 min
Impulse withstand voltage
between power terminals: 5 kV
Impulse withstand voltage
between exposed non-current-carrying metal parts: 5 kV
Noise immunity
+/- 1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 us, 1-ns rise)
Static immunity
Mulfunction: 4 kV Destruction: 8 kV
Vibration resistance (Destruction)
10 to 55 Hz, 0.75 mm single amplitude each in X, Y, and Z directions for 2 hours
Vibration resistance (Malfunction)
10 to 55 Hz, 0.5 mm single amplitude each in X, Y, and Z directions for 10 min
Shock resistance (Destruction)
1000 m/s**2, 3 times each 6 directions
Shock resistance (Malfunction)
100 m/s**2, 3 times each 6 directions
Mechanical life expectancy (relayoutput)
10000000 operations min. (under no load at 1800 operations/h)
Electrical life expectancy (relay output)
100000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
Degree of protection
IP30(Terminal Block: IP20)
Weight (Main)
Approx. 120 g

Returns Policy

You may return most new, unopened items within 30 days of delivery for a full refund. We'll also pay the return shipping costs if the return is a result of our error (you received an incorrect or defective item, etc.).

You should expect to receive your refund within four weeks of giving your package to the return shipper, however, in many cases you will receive a refund more quickly. This time period includes the transit time for us to receive your return from the shipper (5 to 10 business days), the time it takes us to process your return once we receive it (3 to 5 business days), and the time it takes your bank to process our refund request (5 to 10 business days).

If you need to return an item, simply login to your account, view the order using the "Complete Orders" link under the My Account menu and click the Return Item(s) button. We'll notify you via e-mail of your refund once we've received and processed the returned item.

Shipping

We can ship to virtually any address in the world. Note that there are restrictions on some products, and some products cannot be shipped to international destinations.

When you place an order, we will estimate shipping and delivery dates for you based on the availability of your items and the shipping options you choose. Depending on the shipping provider you choose, shipping date estimates may appear on the shipping quotes page.

Please also note that the shipping rates for many items we sell are weight-based. The weight of any such item can be found on its detail page. To reflect the policies of the shipping companies we use, all weights will be rounded up to the next full pound.

Recently Viewed Products