- Contact configuration
- 2 NO, 2 NC
- Terminal capacity (flexible with ferrule)
- 1 x (0.75 - 2.5) mm², Control circuit cables
- Rated operational current for specified heat dissipation (In)
- 80 A
- 10.11 Short-circuit rating
- Is the panel builder's responsibility. The specifications for the switchgear must be observed.
- Rated operational power at AC-3, 380/400 V, 50 Hz
- 37 kW
- Conventional thermal current ith (3-pole, enclosed)
- 80 A
- Rated operational power at AC-4, 380/400 V, 50 Hz
- 20 kW
- Rated operational current (Ie) at AC-4, 440 V
- 40 A
- Terminal capacity (copper band)
- 2 x (6 x 16 x 0.8) mm (Number of segments x width x thickness), Main cables
- Rated control supply voltage (Us) at AC, 50 Hz - min
- 230 V
- 10.4 Clearances and creepage distances
- Meets the product standard's requirements.
- Number of contacts (normally closed) as main contact
- 0
- Short-circuit current rating (high fault at 480 V)
- 65 kA, CB, SCCR (UL/CSA)
- Conventional thermal current ith at 55°C (3-pole, open)
- 94 A
- Rated operational power (NEMA)
- 44.7 kW
- 10.2.3.1 Verification of thermal stability of enclosures
- Meets the product standard's requirements.
- Ambient storage temperature - min
- 40 °C
- Fitted with:
- Mirror contact
- Rated breaking capacity at 380/400 V
- 800 A
- Short-circuit current rating (basic rating)
- 600 A, max. CB, SCCR (UL/CSA)
- Rated control supply voltage (Us) at AC, 50 Hz - max
- 230 V
- Rated breaking capacity at 660/690 V
- 650 A
- Rated operational current (Ie) at DC-1, 220 V
- 70 A
- Special purpose rating of elevator control
- 65 A, 480 V 60 Hz 3-ph, (UL/CSA)
- Ambient operating temperature - max
- 60 °C
- Assigned motor power at 115/120 V, 60 Hz, 1-phase
- 7.5 HP
- Rated operational power at AC-4, 440 V, 50 Hz
- 25 kW
- Electrical connection type of main circuit
- Screw connection
- Number Of Poles
- Three-pole
- Ambient operating temperature - min
- -25 °C
- 10.6 Incorporation of switching devices and components
- Does not apply, since the entire switchgear needs to be evaluated.
- 10.2.6 Mechanical impact
- Does not apply, since the entire switchgear needs to be evaluated.
- 10.3 Degree of protection of assemblies
- Does not apply, since the entire switchgear needs to be evaluated.
- Application
- Contactors for Motors
- Operating frequency
- 3600 mechanical Operations/h (AC operated)
- Voltage type
- AC
- Short-circuit protection rating (type 1 coordination) at 400 V
- 250 A gG/gL
- Product category
- Contactors
- Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V
- 40 A
- Power consumption, pick-up, 50 Hz
- 328 VA, Dual-frequency coil in a cold state and 1.0 x Us
- Heat dissipation capacity Pdiss
- 0 W
- Assigned motor power at 460/480 V, 60 Hz, 3-phase
- 60 HP
- Special purpose rating of tungsten incandescent lamps
- 100 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
- Switching time (AC operated, make contacts, opening delay) - min
- 9 ms
- Continuous ampere rating
- 80 A
- Rated operational current (Ie) at AC-4, 500 V
- 40 A
- Rated operational power at AC-3, 240 V, 50 Hz
- 27.5 kW
- Terminal capacity (solid/stranded AWG)
- 18 - 14, Control circuit cables
- 10.9.2 Power-frequency electric strength
- Is the panel builder's responsibility.
- Degree of protection
- IP00
- Overvoltage category
- III
- Switching time (AC operated, make contacts, opening delay) - max
- 14 ms
- Ambient storage temperature - max
- 80 °C
- Pollution degree
- 3
- Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V
- 110 A
- Power consumption, pick-up, 60 Hz
- 328 VA, Dual-frequency coil in a cold state and 1.0 x Us
- Switching time (AC operated, make contacts, closing delay) - max
- 20 ms
- Rated impulse withstand voltage (Uimp)
- 8000 V AC
- Connection
- Screw connection
- Tightening torque
- 1.2 Nm, Screw terminals, Control circuit cables
- Rated operational power at AC-4, 660/690 V, 50 Hz
- 26 kW
- Conventional thermal current ith (1-pole, enclosed)
- 200 A
- Rated operational current (Ie) at AC-3, 660 V, 690 V
- 65 A
- Type
- Full voltage non-reversing contactor
- 10.2.2 Corrosion resistance
- Meets the product standard's requirements.
- 10.2.4 Resistance to ultra-violet (UV) radiation
- Meets the product standard's requirements.
- 10.2.7 Inscriptions
- Meets the product standard's requirements.
- Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
- 80 A
- Number of contacts (normally open contacts)
- 2
- Switching time (AC operated, make contacts, closing delay) - min
- 14 ms
- Short-circuit protection rating (type 2 coordination) at 400 V
- 160 A gG/gL
- Special purpose rating of ballast electrical discharge lamps
- 100 A (600V 60Hz 3phase, 347V 60Hz 1phase)
- Number of auxiliary contacts (normally open contacts)
- 2
- Special purpose rating of definite purpose rating
- 80 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
- Shock resistance
- 5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
- Rated operational current (Ie) at DC-1, 110 V
- 110 A
- Assigned motor power at 230/240 V, 60 Hz, 3-phase
- 30 HP
- Drop-out voltage
- AC operated: 0.6 - 0.3 x UC, AC operated
- Power consumption, sealing, 60 Hz
- 37.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
- Resistance per pole
- .6 m?
- Ambient operating temperature (enclosed) - min
- 25 °C
- Stripping length (control circuit cable)
- 10 mm
- 10.12 Electromagnetic compatibility
- Is the panel builder's responsibility. The specifications for the switchgear must be observed.
- Special purpose rating of refrigeration control (CSA only)
- 540 A, LRA 480 V 60 Hz 3phase; (CSA)
- Amperage Rating
- 170A
- 10.2.5 Lifting
- Does not apply, since the entire switchgear needs to be evaluated.
- Stripping length (main cable)
- 24 mm
- Ambient operating temperature (enclosed) - max
- 40 °C
- Special purpose rating of resistance air heating
- 100 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
- Rated control supply voltage (Us) at DC - min
- 0 V
- Short-circuit current rating (high fault at 600 V)
- 30/100 kA, Fuse, SCCR (UL/CSA)
- Frequency rating
- 50-60 Hz
- 10.8 Connections for external conductors
- Is the panel builder's responsibility.
- Number of main contacts (normally open contact)
- 3
- Rated breaking capacity at 220/230 V
- 800 A
- Screw size
- M10, Terminal screw, Main cables
- Rated operational current (Ie) at AC-4, 400 V
- 40 A
- Terminals
- Screw terminals
- Short-circuit protection rating (type 2 coordination) at 690 V
- 160 A gG/gL
- Assigned motor power at 575/600 V, 60 Hz, 3-phase
- 75 HP
- Protection
- Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
- Power consumption, sealing, 50 Hz
- 5.8 W, Dual-frequency coil in a cold state and 1.0 x Us
- Terminal capacity (stranded)
- 2 x (16 - 50) mm², Main cables
- HP rating - max
- 2, 5/ 7.5, 10, 15, 20, hp (1/3PH @120, 240/208, 240, 480, 600 V)
- Rated breaking capacity at 500 V
- 800 A
- Rated operational power at AC-3, 415 V, 50 Hz
- 48 kW
- Climatic proofing
- Damp heat, cyclic, to IEC 60068-2-30
- Emitted interference
- According to EN 60947-1
- Static heat dissipation, non-current-dependent Pvs
- 5.8 W
- Rated control supply voltage (Us) at DC - max
- 0 V
- 10.9.3 Impulse withstand voltage
- Is the panel builder's responsibility.
- Utilization category
- AC-4: Normal AC induction motors: starting, plugging, reversing, inching
- Coil voltage
- 230 Vac, 50-60 Hz
- Rated operational current (Ie) at AC-3, 440 V
- 80 A
- 10.5 Protection against electric shock
- Does not apply, since the entire switchgear needs to be evaluated.
- Safe isolation
- 690 V AC, Between the contacts, According to EN 61140
- 10.13 Mechanical function
- The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
- 10.9.4 Testing of enclosures made of insulating material
- Is the panel builder's responsibility.
- Number of contacts (normally closed contacts)
- 2
- Heat dissipation per pole, current-dependent Pvid
- 3 W
- Switching capacity (auxiliary contacts, general use)
- 1 A, 250 V DC, (UL/CSA)
- Operating temperature - min
- -25 °C
- Residual current
- 1 mA (with actuation of A1 - A2 by the electronics with "0" signal)
- Rated operational current (Ie) at AC-4, 660 V, 690 V
- 27 A
- Equipment heat dissipation, current-dependent Pvid
- 9 W
- Assigned motor power at 200/208 V, 60 Hz, 3-phase
- 25 HP
- Pick-up voltage
- 0.8 - 1.1 V AC x Uc
- Suitable for
- Also motors with efficiency class IE3
- Operation
- Non-reversing
- Terminal capacity (solid)
- 2 x (0.75 - 2.5) mm², Control circuit cables
- Number of auxiliary contacts (normally closed contacts)
- 2
- Interference immunity
- According to EN 60947-1
- Power consumption
- 37 kW
- 10.2.3.2 Verification of resistance of insulating materials to normal heat
- Meets the product standard's requirements.
- Operating temperature - max
- 60 °C
- 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
- Meets the product standard's requirements.
- Lifespan, mechanical
- 10,000,000 Operations (AC operated)
- Short-circuit protection rating (type 1 coordination) at 690 V
- 200 A gG/gL
- Rated making capacity up to 690 V (cos phi to IEC/EN 60947)
- 1120 A
- Rated operational power at AC-4, 240 V, 50 Hz
- 13 kW
- Rated operational power at AC-4, 500 V, 50 Hz
- 29 kW
- Voltage rating
- 400 V
- Rated operational current (Ie) at DC-1, 60 V
- 110 A
- Rated operational power at AC-4, 220/230 V, 50 Hz
- 11.5 kW
- Rated operational voltage (Ue) at AC - max
- 690 V
- Rated control supply voltage (Us) at AC, 60 Hz - min
- 230 V
- 10.7 Internal electrical circuits and connections
- Is the panel builder's responsibility.
- 10.10 Temperature rise
- The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
- Switching capacity (main contacts, general use)
- 125 A, Maximum motor rating (UL/CSA)
- Rated operational current (Ie) at AC-3, 500 V
- 80 A
- Assigned motor power at 230/240 V, 60 Hz, 1-phase
- 15 HP
- Screwdriver size
- 0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver
- Duty factor
- 100 %
- Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V
- 80 A
- Conventional thermal current ith of main contacts (1-pole, open)
- 225 A
- Rated control supply voltage (Us) at AC, 60 Hz - max
- 230 V
- Arcing time
- 15 ms
- Rated operational power at AC-4, 415 V, 50 Hz
- 24 kW
- Switching capacity (auxiliary contacts, pilot duty)
- A600, AC operated (UL/CSA)
- Rated insulation voltage (Ui)
- 690 V