Additional Information Part Number 109797 Specifications Contact configuration 1 NO Terminal capacity (flexible with ferrule) 1 x (0.75 - 16) mm², Main cables Rated operational current for specified heat dissipation (In) 32 A 10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be observed. Rated operational power at AC-1, 380/400 V, 50 Hz 20 kW...

Additional Information

Part Number
109797

Specifications

Contact configuration
1 NO
Terminal capacity (flexible with ferrule)
1 x (0.75 - 16) mm², Main cables
Rated operational current for specified heat dissipation (In)
32 A
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Rated operational power at AC-1, 380/400 V, 50 Hz
20 kW
Rated operational power at AC-3, 380/400 V, 50 Hz
7.5 kW
Conventional thermal current ith (3-pole, enclosed)
27 A
Rated operational power at AC-4, 380/400 V, 50 Hz
7 kW
Rated control supply voltage (Us) at AC, 50 Hz - min
230 V
10.4 Clearances and creepage distances
Meets the product standard's requirements.
Number of contacts (normally closed) as main contact
0
Short-circuit current rating (high fault at 480 V)
125/70 A, Class J, max. Fuse, SCCR (UL/CSA)
Conventional thermal current ith at 55°C (3-pole, open)
29 A
Rated operational power (NEMA)
11 kW
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Ambient storage temperature - min
40°C
Rated breaking capacity at 380/400 V
180 A
Short-circuit current rating (basic rating)
125 A, max. CB, SCCR (UL/CSA)
Rated control supply voltage (Us) at AC, 50 Hz - max
230 V
Rated breaking capacity at 660/690 V
120 A
Rated operational current (Ie) at DC-1, 220 V
32 A
Special purpose rating of elevator control
5 HP, 240 V 60 Hz 3-ph, (UL/CSA)
Ambient operating temperature - max
60°C
Assigned motor power at 115/120 V, 60 Hz, 1-phase
2 HP
Electrical connection type of main circuit
Screw connection
Number Of Poles
Four-pole
Ambient operating temperature - min
-25°C
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Application
Contactors for 4 pole electric consumers
Operating frequency
5000 mechanical Operations/h (DC operated)
Voltage type
AC
Short-circuit protection rating (type 1 coordination) at 400 V
63 A gG/gL
Product category
Contactors
Rated operational power at AC-1, 500 V, 50 Hz
26 kW
Power consumption, pick-up, 50 Hz
50 VA, Dual-frequency coil in a cold state and 1.0 x Us
Heat dissipation capacity Pdiss
0 W
Assigned motor power at 460/480 V, 60 Hz, 3-phase
15 HP
Special purpose rating of tungsten incandescent lamps
40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
Switching time (AC operated, make contacts, opening delay) - min
8 ms
Continuous ampere rating
32 A
Rated operational power at AC-3, 240 V, 50 Hz
5.5 kW
Terminal capacity (solid/stranded AWG)
18 - 6, Main cables
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Degree of protection
IP00
Overvoltage category
III
Rated operational power at AC-1, 440 V, 50 Hz
23 kW
Switching time (AC operated, make contacts, opening delay) - max
14 ms
Ambient storage temperature - max
80°C
Pollution degree
3
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V
32 A
Power consumption, pick-up, 60 Hz
40 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Switching time (AC operated, make contacts, closing delay) - max
22 ms
Rated impulse withstand voltage (Uimp)
8000 V AC
Connection
Screw connection
Tightening torque
3 Nm, Screw terminals, Main cables
Conventional thermal current ith (1-pole, enclosed)
76 A
Rated operational current (Ie) at AC-3, 660 V, 690 V
12 A
Type
Full voltage non-reversing small contactor
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
18 A
Number of contacts (normally open contacts)
1
Switching time (AC operated, make contacts, closing delay) - min
16 ms
Short-circuit protection rating (type 2 coordination) at 400 V
35 A gG/gL
Special purpose rating of ballast electrical discharge lamps
40 A (480V 60Hz 3phase, 277V 60Hz 1phase)
Number of auxiliary contacts (normally open contacts)
1
Special purpose rating of definite purpose rating
25 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Shock resistance
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Rated operational current (Ie) at DC-1, 110 V
32 A
Assigned motor power at 230/240 V, 60 Hz, 3-phase
10 HP
Drop-out voltage
AC operated: 0.6 - 0.4 x UC, AC operated
Power consumption, sealing, 60 Hz
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us
Resistance per pole
2.7 mΩ
Ambient operating temperature (enclosed) - min
25°C
Stripping length (control circuit cable)
10 mm
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Special purpose rating of refrigeration control (CSA only)
40 A, FLA 480 V 60 Hz 3phase; (CSA)
Amperage Rating
200A
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Stripping length (main cable)
10 mm
Ambient operating temperature (enclosed) - max
40°C
Special purpose rating of resistance air heating
40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
Rated control supply voltage (Us) at DC - min
0 V
Short-circuit current rating (high fault at 600 V)
10/100 kA, Fuse, SCCR (UL/CSA)
Frequency rating
50-60 Hz
10.8 Connections for external conductors
Is the panel builder's responsibility.
Number of main contacts (normally open contact)
4
Rated breaking capacity at 220/230 V
180 A
Screw size
M5, Terminal screw, Main cables
Rated operational current (Ie) at AC-4, 400 V
15 A
Terminals
Screw terminals
Short-circuit protection rating (type 2 coordination) at 690 V
35 A gG/gL
Assigned motor power at 575/600 V, 60 Hz, 3-phase
20 HP
Protection
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Power consumption, sealing, 50 Hz
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us
Terminal capacity (stranded)
1 x 16 mm², Main cables
HP rating - max
2, 5/ 7.5, 10, 15 20 hp (1/3PH @120, 240/ 208, 240, 480, 600 V)
Rated breaking capacity at 500 V
180 A
Rated operational power at AC-1, 415 V, 50 Hz
22 kW
Rated operational power at AC-3, 415 V, 50 Hz
10 kW
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Connection to SmartWire-DT
No
Static heat dissipation, non-current-dependent Pvs
2.1 W
Rated control supply voltage (Us) at DC - max
0 V
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Utilization category
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Coil voltage
230-240 Vac, 50/60 Hz
Rated operational current (Ie) at AC-3, 440 V
18 A
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Safe isolation
440 V AC, Between coil and contactss, According to EN 61140
Used with
DILM32-XHI( C), DILA-XHI(V)( C)
Rated operational power at AC-1, 220/230 V, 50 Hz
12 kW
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Heat dissipation per pole, current-dependent Pvid
2.2 W
Switching capacity (auxiliary contacts, general use)
10 A, 600 V AC, (UL/CSA)
Operating temperature - min
-25°C
Residual current
1 mA (with actuation of A1 - A2 by the electronics with "0" signal)
Equipment heat dissipation, current-dependent Pvid
6.6 W
Assigned motor power at 200/208 V, 60 Hz, 3-phase
7.5 HP
Pick-up voltage
0.8 - 1.1 V AC x Uc
Operation
Non-reversing
Terminal capacity (solid)
1 x (0.75 - 4) mm², Control circuit cables
Number of auxiliary contacts (normally closed contacts)
0
Rated operational power at AC-1, 240 V, 50 Hz
13 kW
Power consumption
7.5 kW
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
Operating temperature - max
60°C
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
Lifespan, mechanical
10,000,000 Operations (AC operated)
Short-circuit protection rating (type 1 coordination) at 690 V
50 A gG/gL
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)
238 A
Number of contacts
1 NO
Rated operational current (Ie) at DC-1, 60 V
32 A
Rated operational voltage (Ue) at AC - max
690 V
Rated control supply voltage (Us) at AC, 60 Hz - min
240 V
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Switching capacity (main contacts, general use)
40 A, Maximum motor rating (UL/CSA)
Rated operational current (Ie) at AC-3, 500 V
18 A
Assigned motor power at 230/240 V, 60 Hz, 1-phase
5 HP
Screwdriver size
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
Duty factor
100 %
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V
18 A
Conventional thermal current ith of main contacts (1-pole, open)
84 A
Rated control supply voltage (Us) at AC, 60 Hz - max
240 V
Rated operational power at AC-1, 690 V, 50 Hz
35 kW
Switching capacity (auxiliary contacts, pilot duty)
P300, DC operated (UL/CSA)
Rated insulation voltage (Ui)
690 V

General

Model Code
DILMP32-10(230V50HZ,240V60HZ)
EAN
4015081093694
Product Length/Depth
97 mm
Product Height
85 mm
Product Width
58 mm
Product Weight
.49 kg
Certifications
CSA
Catalog Notes
Contacts according to EN 50012

Returns Policy

You may return most new, unopened items within 30 days of delivery for a full refund. We'll also pay the return shipping costs if the return is a result of our error (you received an incorrect or defective item, etc.).

You should expect to receive your refund within four weeks of giving your package to the return shipper, however, in many cases you will receive a refund more quickly. This time period includes the transit time for us to receive your return from the shipper (5 to 10 business days), the time it takes us to process your return once we receive it (3 to 5 business days), and the time it takes your bank to process our refund request (5 to 10 business days).

If you need to return an item, simply login to your account, view the order using the "Complete Orders" link under the My Account menu and click the Return Item(s) button. We'll notify you via e-mail of your refund once we've received and processed the returned item.

Shipping

We can ship to virtually any address in the world. Note that there are restrictions on some products, and some products cannot be shipped to international destinations.

When you place an order, we will estimate shipping and delivery dates for you based on the availability of your items and the shipping options you choose. Depending on the shipping provider you choose, shipping date estimates may appear on the shipping quotes page.

Please also note that the shipping rates for many items we sell are weight-based. The weight of any such item can be found on its detail page. To reflect the policies of the shipping companies we use, all weights will be rounded up to the next full pound.

Recently Viewed Products