- Product Net Width
- 140 mm
- Product Net Depth / Length
- 180.5 mm
- Product Net Height
- 227 mm
- Product Net Weight
- 5.05 kg
- Number of Main Contacts NO
- 3
- Number of Main Contacts NC
- 0
- Number of Auxiliary Contacts NO
- 1
- Number of Auxiliary Contacts NC
- 1
- Rated Operational Voltage
- Main Circuit 690 V
- Rated Frequency (f)
- Main Circuit 50 / 60 Hz
- Conventional Free-air Thermal Current (Ith)
- acc. to IEC 60947-4-1, Open Contactors ? = 40¡C 350 A
- Rated Operational Current AC-1 (Ie)
- (690 V) 40¡C 350 A(690 V) 55¡C 300 A(690 V) 70¡C 240 A
- Rated Operational Current AC-3 (Ie)
- (415 V) 55¡C 210 A(440 V) 55¡C 210 A(500 V) 55¡C 210 A(690 V) 55¡C 210 A(380 / 400 V) 55¡C 210 A(220 / 230 / 240 V) 55¡C 210
- Rated Operational Power AC-3 (Pe)
- (415 V) 110 kW(440 V) 110 kW(500 V) 132 kW(690 V) 160 kW(380 / 400 V) 110 kW(220 / 230 / 240 V) 59 kW
- Rated Breaking Capacity AC-3
- 8 x Ie AC-3
- Rated Making Capacity AC-3
- 10 x Ie AC-3
- Short-Circuit Protective Devices
- gG Type Fuses 400 A
- Rated Short-time Withstand Current Low Voltage (Icw)
- at 40¡C Ambient Temp, in Free Air, from a Cold State 10 s 1700 Aat 40¡C Ambient Temp, in Free Air, from a Cold State 15 min 400 Aat 40¡C Ambient Temp, in Free Air, from a Cold State 1 min 1000 Aat 40¡C Ambient Temp, in Free Air, from a Cold State 1 s 2500 Aat 40¡C Ambient Temp, in Free Air, from a Cold State 30 s 1200 A
- Maximum Breaking Capacity
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2200 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2000 A
- Maximum Electrical Switching Frequency
- (AC-1) 300 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 300 cycles per hour
- Rated Operational Current DC-1 (Ie)
- (110 V) 2 Poles in Series, 40¡C 350 A(220 V) 3 Poles in Series, 40¡C 350 A
- Rated Operational Current DC-3 (Ie)
- (110 V) 2 Poles in Series, 40¡C 350 A(220 V) 3 Poles in Series, 40¡C 350 A
- Rated Operational Current DC-5 (Ie)
- (110 V) 2 Poles in Series, 40¡C 350 A(220 V) 3 Poles in Series, 40¡C 350 A
- Rated Insulation Voltage (Ui)
- acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
- Rated Impulse Withstand Voltage (Uimp)
- Main Circuit 8 kV
- Mechanical Durability
- 5 million
- Maximum Mechanical Switching Frequency
- 300 cycles per hour
- Coil Operating Limits
- (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at ? ² 70¡C)
- Rated Control Circuit Voltage (Uc)
- 50 Hz 100 ... 250 V60 Hz 100 ... 250 VDC Operation 100 ... 250 V
- Coil Consumption
- Holding at Max. Rated Control Circuit Voltage 50 Hz 10 VáAHolding at Max. Rated Control Circuit Voltage 60 Hz 10 VáAHolding at Max. Rated Control Circuit Voltage DC 2 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 470 VáAPull-in at Max. Rated Control Circuit Voltage 60 Hz 470 VáAPull-in at Max. Rated Control Circuit Voltage DC 520 W
- Operate Time
- Between Coil De-energization and NC Contact Closing 40 .... 50 msBetween Coil De-energization and NO Contact Opening 43 ... 53 msBetween Coil Energization and NC Contact Opening 45 ... 85 msBetween Coil Energization and NO Contact Closing 50 ... 90 ms
- Connecting Capacity Main Circuit
- Bar 32 mm?Rigid Al-Cable 2 x 95 ... 120 mm?Rigid Cu-Cable 16 ... 240 mm?
- Connecting Capacity Auxiliary Circuit
- Flexible with Ferrule 1x 0.75 ... 2.5 mm?Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm?Flexible 2x0.75 ... 2.5 mm?Solid 2 x 1 ... 4 mm?Stranded 2 x 1 .... 4 mm?
- Degree of Protection
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
- Terminal Type
- Main Circuit: Bars
- Object Classification Code
- Q
- ETIM 4
- EC000066 - Magnet contactor, AC-switching
- ETIM 5
- EC000066 - Magnet contactor, AC-switching
- EClass
- V11.0 : 27371003
- IDEA Granular Category Code (IGCC)
- 4755 >> Contactors
- E-Number (Finland)
- 3709247
- E-Number (Norway)
- 4115275
- E-Number (Sweden)
- 3228306
- Ambient Air Temperature
- Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50¡CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70¡CClose to Contactor for Storage -40 ... 70¡C
- Maximum Operating Altitude Permissible
- Without Derating 3000 m
- Resistance to Shock acc. to IEC 60068-2-27
- Shock Direction: A 5 gShock Direction: B1 5 gShock Direction: B2 5 gShock Direction: C1 5 gShock Direction: C2 5 g
- RoHS Status
- Following EU Directive 2011/65/EU
- Maximum Operating Voltage UL/CSA
- Main Circuit 600 V
- General Use Rating UL/CSA
- (600 V AC) 300 A
- Horsepower Rating UL/CSA
- (200 V AC) Three Phase 60 hp(208 V AC) Three Phase 60 hp(220 ... 240 V AC) Three Phase 75 hp(440 ... 480 V AC) Three Phase 150 hp(550 ... 600 V AC) Three Phase 200 hp
- Minimum Order Quantity
- 1 piece
- Customs Tariff Number
- 85364900
- Replacement Product ID (NEW)
- 1SFL527002R1311