- Product Net Width
- 438 mm
- Product Net Depth / Length
- 244 mm
- Product Net Height
- 392 mm
- Product Net Weight
- 33 kg
- Number of Main Contacts NO
- 3
- Number of Main Contacts NC
- 0
- Number of Auxiliary Contacts NO
- 1
- Number of Auxiliary Contacts NC
- 1
- Rated Operational Voltage
- Main Circuit 1000 V
- Rated Frequency (f)
- Main Circuit 50 / 60 Hz
- Conventional Free-air Thermal Current (Ith)
- acc. to IEC 60947-4-1, Open Contactors ˜ = 40°C 1650 A
- Rated Operational Current AC-1 (Ie)
- (1000 V) 40°C 1650 A(1000 V) 55°C 1450 A(1000 V) 70°C 1270 A(690 V) 40°C 1650 A(690 V) 55°C 1450 A(690 V) 70°C 1270 A
- Rated Operational Current AC-3 (Ie)
- (415 V) 55°C 1060 A(440 V) 55°C 1060 A(500 V) 55°C 970 A(690 V) 55°C 970 A(1000 V) 55°C 400 A(380 / 400 V) 55°C 1060 A(220 / 230 / 240 V) 55°C 1060
- Rated Operational Power AC-3 (Pe)
- (415 V) 630 kW(440 V) 710 kW(500 V) 710 kW(690 V) 1000 kW(1000 V) 600 kW(380 / 400 V) 560 kW(220 / 230 / 240 V) 315 kW
- Rated Making Capacity AC-3
- 10 x Ie AC-3
- Rated Short-time Withstand Current Low Voltage (Icw)
- at 40°C Ambient Temp, in Free Air, from a Cold State 10 s 10000 Aat 40°C Ambient Temp, in Free Air, from a Cold State 15 min 2200 Aat 40°C Ambient Temp, in Free Air, from a Cold State 1 min 5500 Aat 40°C Ambient Temp, in Free Air, from a Cold State 1 s 12000 Aat 40°C Ambient Temp, in Free Air, from a Cold State 30 s 7500 A
- Maximum Breaking Capacity
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 12000 A
- Maximum Electrical Switching Frequency
- (AC-1) 60 cycles per hour(AC-2 / AC-4) 60 cycles per hour(AC-3) 60 cycles per hour
- Rated Operational Current DC-1 (Ie)
- (110 V) 1-Pole, 40°C 1650 A(110 V) 2 Poles in Series, 40°C 1650 A(220 V) 3 Poles in Series, 40°C 1650 A(600 V) 3 Poles in Series, 40°C 1650 A(850 V) 3 Poles in Series, 40°C 1650 A
- Rated Insulation Voltage (Ui)
- acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 1000 V
- Rated Impulse Withstand Voltage (Uimp)
- Main Circuit 8 kV
- Mechanical Durability
- 0.5 million
- Maximum Mechanical Switching Frequency
- 300 cycles per hour
- Coil Operating Limits
- (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at ¸ ‰¤ 70°C)
- Rated Control Circuit Voltage (Uc)
- 50 Hz 100 ... 250 V60 Hz 100 ... 250 VDC Operation 100 ... 250 V
- Coil Consumption
- Holding at Max. Rated Control Circuit Voltage 50 Hz 48 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 48 V·AHolding at Max. Rated Control Circuit Voltage DC 20.5 V·APull-in at Max. Rated Control Circuit Voltage 50 Hz 2450 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 2450 V·APull-in at Max. Rated Control Circuit Voltage DC 2290 V·A
- Operate Time
- Between Coil De-energization and NC Contact Closing 35 ... 55 msBetween Coil De-energization and NO Contact Opening 35 ... 55 msBetween Coil Energization and NC Contact Opening 50 ... 80 msBetween Coil Energization and NO Contact Closing 50 ... 80 ms
- Connecting Capacity Main Circuit
- Bar 100 mm²
- Connecting Capacity Auxiliary Circuit
- Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²
- Degree of Protection
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
- Terminal Type
- Main Circuit: Bars
- Object Classification Code
- Q
- ETIM 4
- EC000066 - Magnet contactor, AC-switching
- ETIM 5
- EC000066 - Magnet contactor, AC-switching
- EClass
- V11.0 : 27371003
- IDEA Granular Category Code (IGCC)
- 4758 >> Iec Contactors
- E-Number (Finland)
- 3709258
- E-Number (Norway)
- 4115390
- E-Number (Sweden)
- 4115390
- Ambient Air Temperature
- Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50°CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70°CClose to Contactor for Storage -40 ... 70°C
- Maximum Operating Altitude Permissible
- Without Derating 3000 m
- RoHS Status
- Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- NEMA Size
- 8
- Horsepower Rating NEMA
- (230 V AC) Three Phase 450 Hp(460 V AC) Three Phase 900 Hp(575 V AC) Three Phase 900 Hp
- Maximum Operating Voltage UL/CSA
- Main Circuit 1000 V
- General Use Rating UL/CSA
- (1000 V AC) 1650 A(600 V AC) 1650 A
- Horsepower Rating UL/CSA
- (220 ... 240 V AC) Three Phase 450 hp(440 ... 480 V AC) Three Phase 900 hp(550 ... 600 V AC) Three Phase 1150 hp
- Minimum Order Quantity
- 1 piece
- Customs Tariff Number
- 85364900