Additional Information
- Part Number
- 1SDA070918R1
- UNSPSC
- 39121615
- ETIM
- Group Code : EG000017
- Group Description : Low-voltage Industrial Components
- Class Description : Power circuit-breaker for trafo/generator/installation protection
- Class Code : EC000228
- Version : 7
Additional Information
- Current Type
- AC
- Electrical Durability
- Ue =< 440 V 15000 cycleUe = 500 ... 690 V 15000 cycle30 cycles per hour
- Mechanical Durability
- 25000 cycle60 cycles per hour
- Number of Poles
- 3
- Power Loss
- 34 W
- Product Main Type
- SACE Emax 2
- Product Name
- Air Circuit Breaker
- Product Type
- Air Circuit Breaker
- Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
- 100 %
- Rated Current (In)
- 800 A
- Rated Voltage (Ur)
- 690 V
- Rated Impulse Withstand Voltage (Uimp)
- acc. to IEC 60947-2 12 kV
- Rated Insulation Voltage (Ui)
- AC 1000 V
- Rated Operational Voltage
- 690 V AC
- Rated Service Short-Circuit Breaking Capacity (Ics)
- (220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(660 V AC) 85 kA(690 V AC) 85 kA
- Rated Short-time Withstand Current Low Voltage (Icw)
- for 1 s 85 kAfor 3 s 66 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu)
- (400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(525 V AC) 85 kA(690 V AC) 85 kA
- Rated Uninterrupted Current (Iu)
- 800 A
- Recommended Screw Driver
- Main Circuit M12
- Release
- Ekip Hi-Touch LSI
- Release Type
- EL
- Short-Circuit Performance Level
- H
- Standards
- IEC
- Sub-type
- E2.2
- Terminal Connection Type
- Rear flat Horizontal
- Terminal Type
- Bolt
- Tightening Torque
- 70 N·m
- Version
- F
- CAD Dimensional Drawing
- 1SDH001252R0083
Dimensions
- Product Net Width
- 276 mm
- Product Net Height
- 371 mm
- Product Net Depth / Length
- 270 mm
- Product Net Weight
- 41 kg
ABB EcoSolutions
- ABB EcoSolutions
- Yes
Eco Transparency
- Environmental Product Declaration - EPD
- 9AKK108468A1902 9AKK108468A1909
Classifications
- ETIM 9
- EC000228 - Power circuit-breaker for trafo/generator/installation protection
- IDEA Granular Category Code (IGCC)
- 4926 >> Air circuit breakers
- Object Classification Code
- Q
- WEEE Category
- 5. Small Equipment (No External Dimension More Than 50 cm)
- EClass
- V11.1 : 27370409
Environmental
- Environmental Information
- 9AKK10103A1038 9AKK108467A6707
- REACH Declaration
- 9AKK108466A1425
- RoHS Information
- 9AKK108466A1424
- RoHS Status
- Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- SCIP
- 1014a0b7-3d01-430e-b024-3005f92f1d8a Italy (IT)
- Simplified SCIP
- 25bac095-b6c3-4429-94a5-2447b15805a2 Spain (ES)fe23c86f-5cd8-42e6-9a02-7bf387b49881 Belgium (BE)86db4dbf-dd75-4af2-80e1-257781b6a63a Hungary (HU)4fce85c7-e15f-418e-8ce9-c06df22eb5b2 Croatia (HR)d7fc2784-3200-4d72-879d-b0f17b0dc811 Norway (NO)5ca65eb9-2f40-4297-b023-36a1e8565e26 Poland (PL)823660bb-e7b7-4a15-9ea5-86a446afd7bc Hungary (HU)50c048fa-93cc-4a79-b03b-ff197cf0de57 Czech Republic (CZ)6daa208c-3345-40ed-8f46-f6c82e3899ae Denmark (DK)7213f52a-e703-4040-b194-908536d9da0c Estonia (EE)33226188-82f3-46a0-b637-a832408a6e06 Germany (DE)6a92541d-4eaf-4030-aa9e-04bcb5bb131e Germany (DE)23a37f72-d2f1-475e-9c25-4a7d76b95a2d Germany (DE)3f204d93-0045-413e-bbfc-532d6f5e6aef Germany (DE)61181626-1585-4ef8-8239-89afa4883d62 Sweden (SE)0cf2b609-b33a-413a-bf1b-7ba0346a0de3 Bulgaria (BG)d58d97e0-c776-40aa-b40c-15eaaf3d57e5 Belgium (BE)e0ded06d-fa8b-4ca2-abe6-d48d89564cfc France (FR)be7b3654-ab2a-45f6-bcf1-f6d66a99750e Greece (GR)994dd9b9-cea9-4a2e-9709-b9c90d0e9c4f Finland (FI)7eb529be-52a6-42b4-8374-28b655a9ee44 Netherlands (NL)c702cc5e-7aab-4d5c-9105-87962e5b890b France (FR)4c772fd1-4873-46d5-9ba8-3c1a8599f875 Poland (PL)bffb6204-ff7e-4964-b30b-95a1dd2a51c9 Poland (PL)054f8597-29bf-476c-935a-c2127fe0e5a8 Sweden (SE)e3d537b5-230c-4e49-bbd7-7c902d414ea6 Portugal (PT)
Circular Value
- Circular Design Principles Recyclability Rate
- Design for Closing Resource Loops - Standard EN45555 - 79.1 %
- Conflict Minerals Reporting Template (CMRT)
- 9AKK108467A5658
- End of Life Instructions
- 9AKK108468A2361
- Group Waste to Landfill Target
- UL 2799 Zero Waste To Landfill Validation available
- Toxic Substances Control Act - TSCA
- 9AKK108467A8326
Ordering
- Order Code US and Canada
- Z2HPEFBJ200A000000XX
- Minimum Order Quantity
- 1 piece
- Customs Tariff Number
- 85362090