Additional Information
- Part Number
- 1SDA068524R1
- UNSPSC
- 39120000
- ETIM
- Group Code : EG000017
- Group Description : Low-voltage Industrial Components
- Class Description : Power circuit-breaker for trafo/generator/installation protection
- Class Code : EC000228
- Version : 7
Additional Information
- Circuit Breaker Type to be Associated
- Power Distribution
- Connecting Capacity Main Circuit
- Busbar 85..200 mm²
- Current Type
- AC
- Electrical Durability
- 120 cycles per hour8000 cycle
- Mechanical Durability
- 240 cycles per hour25000 cycle
- Number of Poles
- 3
- Opening Time
- CB with SOR 15 msCB with UVR 15 ms
- Order Multiple
- 1 piece
- Power Loss
- at Rated Operating Conditions per Pole 8.90 W
- Product Main Type
- SACE Tmax XT
- Product Name
- Moulded Case Circuit Breaker
- Product Type
- Automatic Circuit Breaker
- Rated Current (In)
- 160 A
- Rated Frequency (f)
- 50/60 Hz
- Rated Voltage (Ur)
- 690 V AC
- Rated Impulse Withstand Voltage (Uimp)
- 8 kV
- Rated Insulation Voltage (Ui)
- 1000 V AC
- Rated Operational Voltage
- 690 V AC
- Rated Service Short-Circuit Breaking Capacity (Ics)
- (220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 45 kA(690 V AC) 15 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu)
- (220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 45 kA(690 V AC) 15 kA
- Rated Uninterrupted Current (Iu)
- 160 A
- Recommended Screw Driver
- Main Circuit M8
- Release
- Ekip LSI
- Release Type
- EL
- Short-Circuit Performance Level
- H
- Standards
- IEC
- Sub-type
- XT4
- Terminal Connection Type
- Front
- Terminal Type
- Bolt
- Tightening Torque
- 8 N·m
- Version
- F
- CAD Dimensional Drawing
- 1SDH002230A1003
Dimensions
- Product Net Width
- 105 mm
- Product Net Height
- 160 mm
- Product Net Depth / Length
- 82.5 mm
- Product Net Weight
- 2.5 kg
ABB EcoSolutions
- ABB EcoSolutions
- Yes
Eco Transparency
- Environmental Product Declaration - EPD
- 9AKK108468A1898
Classifications
- ETIM 9
- EC000228 - Power circuit-breaker for trafo/generator/installation protection
- Object Classification Code
- Q
- WEEE Category
- 5. Small Equipment (No External Dimension More Than 50 cm)
- EClass
- V11.1 : 27370409
Environmental
- Environmental Information
- 9AKK107991A8215 9AKK108467A6707
- REACH Declaration
- 9AKK108466A1425
- RoHS Information
- 9AKK108466A1424
- RoHS Status
- Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- SCIP
- 6c060105-007b-426b-868a-47abbf32990d Italy (IT)
- Simplified SCIP
- 1f6df7ae-81cb-4203-b88f-c9e0ce3c80fc Greece (GR)594b243a-41c3-4148-9c38-7ee740f97f6f Portugal (PT)30120d4f-0247-4a26-a4cf-9c9837eac203 Bulgaria (BG)06a41a5d-c19b-4c0b-b620-825d933ef324 Sweden (SE)0f85d3f4-99fa-4bba-9173-4dd509620dc7 Poland (PL)d6eb10a0-7d0a-4ffc-80ba-b9cb8e8d7e19 Germany (DE)9b4f6201-11ec-4d6b-a8e8-6017d271f41d Croatia (HR)7f827d8b-850f-4f07-b971-2ff2128558af Czech Republic (CZ)90cca48d-5582-495e-bc66-eb9bee00a710 Poland (PL)5ed68dae-4e75-41c2-98cd-a25bb747a865 Netherlands (NL)9ce97b17-9c37-44df-b22d-ca1e3530b54e Netherlands (NL)5e3b3e07-126a-430c-94f9-575edf250ba2 Estonia (EE)3796915d-9b97-4526-bd59-8b0d8e8e28a7 Netherlands (NL)09ddc47f-6fcb-4c99-baec-5e4656e1ff71 Germany (DE)9b730da1-a6cc-47bd-92e1-2d3d96735de1 Denmark (DK)7bbd843c-b9c8-4557-b3e5-89cdc8a02d8f France (FR)d4fd2ca2-f1f7-4491-8514-bf656dc2b12c Sweden (SE)0344c3c8-cead-4a10-8c3b-032f3917c1e8 Germany (DE)75ac2893-b89d-4777-9d68-0479b91a9544 Germany (DE)e610ecff-5d14-4126-b6e9-442e3668e3eb France (FR)b539c7a6-c4c5-4d23-85ef-eaca2235c514 Netherlands (NL)ab48002c-40f9-4e35-8dea-d7d55def9e95 Spain (ES)37ccc43c-1b79-4561-ac0f-a62399b3d2f7 Netherlands (NL)758a0320-b742-4d76-a154-6a07b397c740 Poland (PL)b32ce7cd-3d9d-42cc-8d40-a328c78f62ce Norway (NO)7c80d365-f207-4088-b463-d1110f842217 Finland (FI)
Circular Value
- Circular Design Principles Recyclability Rate
- Design for Closing Resource Loops - Standard EN45555 - 58.5 %
- Conflict Minerals Reporting Template (CMRT)
- 9AKK108467A5658
- End of Life Instructions
- 9AKK108468A2352
- Group Waste to Landfill Target
- UL 2799 Zero Waste To Landfill Validation available
- Toxic Substances Control Act - TSCA
- 9AKK108467A8326
Ordering
- Order Code US and Canada
- XT4HE3160FFF000XXX
- Minimum Order Quantity
- 1 piece
- Customs Tariff Number
- 85362090