Additional Information
- Part Number
- LP1D80004BD
- UNSPSC
- 39121529
- Tariff Code
- 8536490075
- Country of Origin
- CZ
Environment
- Product Certifications
- BV || CCC || CSA || DNV || EAC || GL || LROS (Lloyds register of shipping) || UL || UKCA
- Height
- 127 mm
- Standards
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
- Net Weight
- 2.685 kg
- Flame Retardance
- V1 conforming to UL 94
- Ip Degree Of Protection
- IP20 front face IEC 60529
- Mechanical Robustness
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 3 Gn, 5...300 Hz) || shocks contactor open 8 Gn for 11 ms) || shocks contactor closed 10 Gn for 11 ms)
- Operating Altitude
- 0...9842.52 ft (0...3000 m)
- Fire Resistance
- 850°C IEC 60695-2-1
- Width
- 96 mm
- Depth
- 181 mm
- Permissible Ambient Air Temperature Around The Device
- -40-60°C || 60-70°C with derating
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP110205EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Circularity Profile
- N/A
- Eu Rohs Directive
- Compliant
Complementary
- Power Dissipation Per Pole
- 12.5 W AC-1 || 5.1 W AC-3 || 5.1 W AC-3e
- Average Impedance
- 0.8 mOhm - Ith 125 A 50 Hz for power circuit
- [Ith] Conventional Free Air Thermal Current
- 125 A (at 60°C) for power circuit
- Control Circuit Voltage Limits
- 0.1...0.3 Uc -40-70°C drop-out DC || 0.85...1.1 Uc -40-55°C operational DC || 1...1.1 Uc 55-70°C operational DC
- Mounting Support
- rail || plate
- Contact Compatibility
- M4
- Control Circuit Type
- DC DC standard
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pollution Degree
- 3
- Hold-In Power Consumption In W
- 22-22 W 20°C
- Rated Breaking Capacity
- 1100 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity
- 1100 A at 440 V for power circuit conforming to IEC 60947
- Associated Fuse Rating
- 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947
- Pole Contact Composition
- 4 NO
- Connections - Terminals
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid || power circuit: connector 1 4-50 mm² - cable stiffness: flexible without cable end || power circuit: connector 2 4-25 mm² - cable stiffness: flexible without cable end || power circuit: connector 1 4-50 mm² - cable stiffness: flexible with cable end || power circuit: connector 2 4-16 mm² - cable stiffness: flexible with cable end || power circuit: connector 1 4-50 mm² - cable stiffness: solid || power circuit: connector 2 4-25 mm² - cable stiffness: solid || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end
- Coil Technology
- without built-in suppressor module
- Time Constant
- 75 ms
- Operating Time
- 6...20 ms opening || 20...35 ms closing
- Maximum Operating Rate
- 3600 cyc/h 60°C
- Tightening Torque
- control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m lugs-ring terminals pozidriv No 2
- Electrical Durability
- 0.8 Mcycles 125 A AC-1 <= 440 V
- Mechanical Durability
- 4 Mcycles
- Inrush Power In W
- 22-22 W 20°C)
- Compatibility Code
- LP1D
- Overvoltage Category
- III
- [Ui] Rated Insulation Voltage
- power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
- [Icw] Rated Short-Time Withstand Current
- 135 A 40°C - 10 min for power circuit || 320 A 40°C - 1 min for power circuit || 640 A 40°C - 10 s for power circuit || 990 A 40°C - 1 s for power circuit
- Protective Cover
- without
Specifications
- [Uc] Control Circuit Voltage
- 24 V DC
- [Ue] Rated Operational Voltage
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Range Of Product
- TeSys Deca
- Contactor Application
- resistive load
- Product Or Component Type
- contactor
- Range
- TeSys
- Utilisation Category
- AC-1 || AC-3 || AC-3e || AC-4
- [Ie] Rated Operational Current
- 125 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 80 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 55 A (at <60°C) at <= 400 V AC AC-4 for power circuit
- Poles Description
- 4P
- Device Short Name
- LP1D